Activate address setting mode for DU
(H5/A9)
This function can be used by commissioning / service engineer to
activate the address setting mode in the following
D
isplay
U
nits
connected to the RS485 interface in EBL128:
Ext. Presentation unit (EPU) 1728
Alert Annunciation unit (AAU) 1735 / 1736
Ext. Fire Brigade Panel (FBP) 1826 / 1828
A specific unit or all units can be activated for address setting.
NOTE!
The units have to be in operation and in quiescent condition,
i.e. the units have to have an address set already.
Action
Text in display
Comments
"Access"
According to chapter
"Access code for service
and maintenance", see
page 104.
Disconnect / Re-connect COM loop
ACCEPT? A1
Scroll to menu A9
Activate address setting mode for DU
ACCEPT? A9
"A"
Activate address setting mode for
DU 0 (9 = All) ACCEPT?
Write the unit's address.
9 = All units.
Press "A" to accept.
"A"
Activate address setting mode for DU
ACCEPT? A9
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.
The address has thereafter to be edited in the unit respectively.