Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
72
turned off. LED "General fault" (L7) is indicating that EBL128 is
in the so called "Boot mode". LEDs "Alarms queued" (L2) are
indicating the Flash memory programming. In the EBL128
display is the following information shown:
Software download in progress......
4.
To the left of the progress bar is a "% indicator". It will show
approx. 90 % when the download is ready and EBL128 will
automatically do a restart.
5.
After the restart the "% indicator" will show 100 %. Close the
dialog box. Regarding the restart, see also chapter "Restart", page
74.
6.
LED "Operation" (L6) will be turned on and LED "General fault"
(L7) and LEDs "Alarms queued" (L2) will be turned off.
21.2
Upgrade of S/W version 1.0.x to version
1.1.x in EBL128 (c.i.e.)
The specific upgrade of
S/W version 1.0.x to version 1.1.x
is unique,
i.e. the normal software download procedure described above
must
not
be followed.
Before download, the PC has to be connected to the RS232 connector
J3 in EBL128 (on the main board).
1.
Start Win128. Do
not
log on to EBL128. In the "Tools" menu
select "Download EBL128 Software…" to open the dialog box
and do the required settings, i.e. mark the checkbox "Download
software", select the path and the S/W file, i.e.
EBL128_110.BIN
.
Also a text file
71
shall be downloaded. Do not forget to mark the
checkbox "Download texts" and select the path and the text file,
e.g.
English_texts_EBL128_110.sst
.
71
The text file contains all the text that will be shown in the EBL12 display.
Normally a new text file will come together with a new S/W file.
NOTE!
If only the text file shall be downloaded, do not mark the checkbox
"Download software".