25.2
Disable zone / address (H2/B2)
All addressable alarm points (also addressable manual call points),
connected to the COM loop, can be individually disabled.
Disabled alarm points (zone – address) are listed in menu H4/U1.
Disabled alarm points (zone – address) can be automatically re-
enabled or they have to be re-enabled via menu H2/B6.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B2.
Disable zone / address
ACCEPT? B2
"A"
Disable zone: 00 Address: 00
ACCEPT?
Write zone number and
address
(e.g. 01 - 01)
Disable zone: 01 Address: 01
ACCEPT?
Press "A" to accept.
"A"
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM ACCEPT?
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours). Press "A" to
accept. LED
"Disablements" (L8) will
light up.
(Default is current time + 3 hours)
"A"
Disable zone: 00 Address: 00
ACCEPT?
If more disablements
shall be done, continue
like above. If not, press
"Return" to menu B2.
Scroll or press "Return"
to menu H2. Scroll or
press "Return" to log off.