The zone(s) will stay in test mode until the test mode is ended
but after 60 minutes or if you press
"Return" two times, you will be logged out from menu H1.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up, and the LEDs "Fire" (L1) in EBL128 will light up, about ten
seconds, then the alarm point will be automatically reset.
A detector in test mode will not be able to activate fault.
After 60 minutes
or
"Return"
"Return"
Zones in test mode: 01, 02, 03, 04
You are no longer in menu
H1 but still in test mode.
NOTE! See chapter "The display in EBL128", page 20
regarding priority order.
(When required:
"Access", "code")
"A"
Zone in TEST MODE:
01 02 03 04 End test: ACCEPT
Press "A" to end the test
mode.
"A"
Test of routing equipment? 0
(1 = Yes, 0 = No) ACCEPT
The LED "Test mode" is
turned OFF.
Some national regulations also require a routine test of the routing equipment. Press "A" for no test or press
"1" and "A" to start such a test. The following will happen:
EBL128 "Fault tx" output will be de-activated
77
, indicated by the LED "Fault tx activated" (L11).
A 60 seconds count-down starts.
After 30 seconds, EBL128 "Fire brigade tx" output (and corresponding programmable outputs type 4 =
routing equipment) will be activated as well, indicated by the LED "Fire brigade tx" (L15).
After another 30 seconds, the test will be ended and all the outputs and LEDs will return to "normal".
"1", "A"
Test of routing equipment in progress.
nn seconds left.
"nn" starts at 60 and will
count down to 00.
Monthly test is completed!
ACCEPT
"A"
Perform monthly test
ACCEPT? H1
Scroll or press "Return" to
log off.
NOTE!
If an alarm point (e.g. a manual call point) is in alarm state
when the test mode is ended, there will not be a fire alarm activated.
Instead the alarm point will be disabled (the "encapsulation function")
and has to be re-enabled again, see menu H2/B6.
When the "Fire door closing" function is used, the fire door will be
closed when the detectors controlling the door are tested via the test
mode.
77
NOTE!
This output is activated in normal state.