Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
EBL128 Operating Instructions V1.1.x
130
32.4
Disable interlocking output (H9/C4)
Interlocking outputs (Type = Interlocking) will be disabled via this
menu but not via menu H2/B3.
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output. If "00/00" is entered,
all
interlocking outputs will
be disabled at the same time.
All interlocking outputs can be disabled.
Disabled interlocking outputs are listed in menu H4/U1.
The LED "Disablements" (L8) is also indicating one or more disabled
interlocking outputs.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 78.
Scroll to menu H9.
Interlocking outputs and inputs
ACCEPT? H9
"A"
Activated interlocking outputs/inputs
ACCEPT? C1
Scroll to menu C4.
Disable interlocking output
ACCEPT? C4
"A"
Disable interlocking output
area 00 point 00 ACCEPT?
Write the area and point,
e.g.: "01", "01"
Disable interlocking output
area 01 point 01 ACCEPT?
Press "A" to accept and/or
"Return" to menu C4.
"A"
Disable interlocking output
ACCEPT? C4
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.