Data Sheet:         

OPTICAL SMOKE ALARM           Model No.  300 - RE  

 

 

Detection 

part 

     Socket 

 

 

 
Description 

 

The ICAS Model 300-RE is an external powered smoke alarm operating on the scattered light principle 

with relay output. It is intended for household or similar residential applications as system detector in combine 
with suitable central unit.   

This model can be powered from an external voltage source (central unit) 9V DC or from an external 

source (central unit) with output voltage in the range from 12V DC to 24V DC. It is activated relay in alarm, 
sound output  and red LED is flashing,  It is possible to use both NO or NC potential less contacts for a 
communication with central unit. 

 Model 300-RE contents as an  special option  a buzzer with a high sound level like self-contained 

smoke alarm. 
It is  best for slow smouldering fires with large smoke particles.  
Model 300-RE is non-latching – the buzzer will sound output for an alarm and relay will be activated only when 
smoke particles are present in the smoke chamber .  

There is  one combined push-buttons / LED indicator light projection lens   and sound outlet on top of 

the smoke alarm. There are six contacts on the bottom side of the detection part  for a possibility  to  contact  the 
socket part. 

The smoke alarm consist of a full covered detection  part with optical chamber,  sounder  and all 

electronics components and of the socked with 6 terminals.  The terminals are numbered. 
 
Terminal description: 

+U DC   

(for using of the power supply voltage from 12V to 24V DC) 

+9V DC  

(for using of the power supply voltage 9V DC)

 

0V  

 

9V

0V

Shield

NO 

 

relay contact – normal open

 

COM   

common relay contact

 

NC 

 

relay contact – normal connect

 

  

 

 

Example

 of the connection to the 9V  

 
 
Installation 
 

1.  Locate smoke alarm it in the middle of the ceiling in living and dining rooms, halls and landings, max. 1.5m 

from the door in bedrooms and  at least  1.5m from wall and at least 1m from lighting fixture or any other 
electrical household equipment.  

2.  Fix socket to the ceiling by two screws and connect correspondent wires from the central unit. The using of 

shielded  cables (AF CEI 20-22 IEC 332) and connection  of the shield to 0V on each position of smoke 
alarms is recommended.  

 