MPX-SNDR-DG V2
SOUNDER MODULE WITH 4
AND 8 SOUNDERS OUTPUTS
MANUAL 210628
MADE IN PORTUGAL - EU
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL | Tel: +351 289 896 560
Email: [email protected] | Technical Support: [email protected] | www.globalfire-equipment.com
TECHNICAL SPECIFICATIONS
SUPPLY VOLTAGE
24V DC to 30V DC
NORMAL OPERATION
6mA ( ) + 5.5mA per activated channel, 50mA on evacuation mode (all sounders)
𝐼
𝑞
EOL RESISTOR
22K Ohms - 1/4 Watts
MAX. CABLE SIZE
2.5 mm²
COLOUR / CASE MATERIAL
White / ABS
OPER. TEMPERATURE / MAX. HUMIDITY
-10
º
C to 50
º
C / 95% RH Non-Condensing
DIMENSIONS / WEIGHT
150 (W) x 90 (L) x 32 (H) mm / 216 g inc. packaging
ORDER CODE
MPX-SNDR-DG - 4 V2
4 SOUNDER MODULE FOR ORION FAMILY
MPX-SNDR-DG - 8 V2
8 SOUNDER MODULE FOR ORION FAMILY
CONNECTIONS
Remove all power before connections!
Connections:
a.
Direct connection (flat cable directly connected
to conventional panel).
i. Connect panel and MPX-SNDR-DG V2 using
molex flat cable.
ii. Set both communication jumpers UP
(option “panel”).
iii. Remove supply jumper.
iv. Power supply from Panel, ensure it won’t
exceed the maximum allowed current from this
source.
b.
Remote connection (remote connection using an
interface module connected to panel).
i. Connect Interface and MPX-SNDR-DG V2 using
molex flat cable.
ii. Set both communication jumpers DOWN
(option “interface”).
iii. Fit the supply jumper. Power supply from
MPX-SNDR-DG V2.