Fire alarm systems 

Address setting tool 

3314 

 

Used for address and mode setting 

COM loop address setting 

Address setting tool 3314 is used to program 
the  COM  loop  address  on  the  analog 
detector  types  33xx  /  430x  and  all  other 
addressable units (33xx and 43xx). 

Mode setting 

The address setting tool 3314 is also used to 
set  the 

NORMAL

,  2330  or  2312  mode  to 

the  units.    See  the  instructions  for  the  unit 
respectively. 

Connection cable 

Some  units  have  flying  leads  for  easier 
connection of 3314.  Some units have screw 
terminals.    A  connection  cable  with 
insulated  crocodile  clips  and  push-on 
terminals is supplied with the address setting 
tool, to be used when required. 

User friendly 

The address setting tool is powered by four 
1.5 V batteries  (LR6 / AA).  

Procedure for reading / writing: 

 

Set  the  ON/OFF  switch  on  the  address 
setting  tool  in  position  "ON".    LED 
"POWER" lights up. Wait for a beep. 

 

Plug  the  analog  detector  contact  pins 
(SA  /  SB)  into  the  address  setting  tool's 
snap  connectors  (SA  /  SB)  or  use  the 
connection cable to connect other units. 

How to read: 

 

Press  the  "READ"  button.  Wait  for  a 
beep  and  read  the  address  and  mode  in 
the display. 

How to write: 

 

Select MODE by pressing the "WRITE" 
and  "READ"  buttons  at  the  same  time 
until  the  marker  in  the  display  is  in  the 
correct MODE position. 

 

Type-in  the  COM  loop  address  and 
press "WRITE".  Wait for a beep. 

 

Press  the  "READ"  button  for  a  check.  
Wait for a beep and read the address and 
the mode. 

Write the COM loop address on the Address 
label on the detector (and the base) or on the 
unit.  

After using the address setting tool, it should 
be  turned  OFF.    (If  the  tool  is  left  not  used 
for 

more 

than 

minutes, 

it 

will 

automatically be turned off.) 

Product applications 

Used  when  analog  detectors  and  other 
addressable  COM  loop  units  are  to  be  used 
in  the  systems  EBL128  /  512  /  512  G3  / 
1000 / 2000. 