INSTALLATION INSTRUCTIONS

 

www.wheelockinc.com 

         

MULTITONE STROBE APPLIANCES

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

GENERAL: 

The Multitone Strobe Appliances are UL Listed under Standard 1971 for Emergency Devices for the Hearing Impaired and UL 
Standard 464 for Audible Signal Appliances.  The LSM strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela 
intensity on axis with low current draw.  They are listed for indoor use with the backboxes specified in these instructions (See 
Mounting Options).  Models with LS, MS and IS strobes are Listed for wall or ceiling mounting; models with LSM strobes are Listed 
for wall mounting. The Multitone Strobe Appliances use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan

 

lens to provide maximum visibility and reliability for effective visible signaling. 

 

Multitone Strobe Appliances can be field set to produce any one of eight commonly used alarm tones.  Sound output can be field set 
to provide either HIGH (HI) dBA or STANDARD (STD) dBA sound output level.   

 

All Multitone Strobe models are designed for use with either filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage.  The 
Multitone Strobe Appliances have separate input terminals for alarm tone activation and strobe activation.  Shunt wires are provided 
to operate both the alarm tone and the strobe simultaneously on a single input circuit (See Wiring Diagram).  All inputs are polarized 
for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). 

NOTE

:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.

  All warnings are printed in bold capital letters. 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  FAILURE TO COMPLY 

WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER 
APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH 
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

WARNING:  THE MULTITONE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL 

AND ALARM TONE BEFORE THEY ARE INSTALLED.  THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG AND 
ADJUSTING A FOUR POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS.  INCORRECT SETTINGS WILL 
RESULT IN IMPROPER PERFORMANCE AND MAY DAMAGE THE PRODUCT, WHICH COULD RESULT IN PROPERTY 
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS

Table 1:  UL Listed Models 

Model 

 

Nominal 

Voltage 

(VDC) 

Rated 

Voltage  

(VDC) 

Strobe 

Candela 

(CD) 

Anechoic 

dBA at  

10 Feet 

Mounting 

Options 

MT-12-LS 12 

10.5-15.6 

15 

87-99  

MT-12-LSM 

12 

10.5-15.6 

  15* 

87-99 

 

MT-12-MS 12 

10.5-15.6 

30 

87-99  

MT-24-LS 24 

20.0-31.0 15  87-99 A,B,C,D 

MT-24-LSM 

24 

20.0-31.0 

  15* 

87-99 

E,F,G 

MT-24-MS 24 

20.0-31.0 

30 

87-99  

MT-24-IS 24 

20.0-31.0 

75 

87-99 

 

MT4-12-LS 12 

10.5-15.6 

15 

87-99   

MT4-12-LSM 

12 

10.5-15.6 

  15* 

87-99 

 

MT4-12-MS 12 

10.5-15.6 

30 87-99   

MT4-24-LS 24 

20.0-31.0 

15 

87-99 H 

MT4-24-LSM 

24 

20.0-31.0 

  15* 

87-99 

 

MT4-24-MS 24 

20.0-31.0 

30 87-99   

MT4-24-IS 24 

20.0-31.0 

75 

87-99  

*15cd models are Listed at 15cd and meet 75cd on axis

 

 

WARNING:  CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND 

SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO 
THE SIGNALING DEVICE. 

 

Copyright 1993-1997, 2000 Wheelock, Inc.  All rights reserved. 

Summary of Contents for MT-12-LS

Page 1: ...f circuit wiring by a Fire Alarm Control Panel FACP NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS ...

Page 2: ... 88 79 75 82 75 Anechoic dBA is measured on axis in a non reflective free field test room using fast meter response For peak dBA measured with peak meter response add 5 dBA to anechoic values shown in Table 3 Reverberant dBA is a minimum UL rating based on sound power measurements in a reverberant test room WARNING MULTITONE STROBE MODELS SET ON CODE 3 TONE WITH STANDARD dBA DO NOT MEET THE 75 dBA...

Page 3: ...plies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies For example an auxiliary power supply that lacks filtering at its output stage either via lack of capacitance and or lack of battery backup across the output may exhibit this characteristic CAUTION Strobes are not designed to be used on coded syste...

Page 4: ...odels Volts 20 0 22 0 24 0 26 0 28 0 31 0 10 5 12 0 15 6 LS DC 1 0 1 1 1 3 1 4 1 5 1 7 0 9 1 0 1 5 FWR 1 0 1 1 1 3 1 4 1 6 1 8 0 9 1 0 1 5 LSM DC 1 0 1 2 1 3 1 4 1 5 1 6 0 9 1 0 1 6 FWR 1 0 1 2 1 3 1 4 1 5 1 7 0 9 1 0 1 5 MS DC 1 0 1 1 1 2 1 4 1 5 1 6 0 9 1 0 1 6 FWR 1 0 1 1 1 2 1 4 1 4 1 6 0 9 1 0 1 4 IS DC 1 1 1 2 1 3 1 3 1 4 1 5 FWR 1 0 1 1 1 2 1 3 1 3 1 4 NOTE ADA guidelines presently specify ...

Page 5: ...T IS BELOW THE 75 dBA MINIMUM CODE REQUIREMENT FOR PUBLIC MODE FIRE PROTECTION STEP 2 Set desired alarm tone as follows refer to Figure 3 and Table 8 Multitone Strobe Appliances are field set for any one of eight alarm tones by setting a four position switch SW1 as shown in Figure 3 and Table 8 Use SW1 POS 2 3 4 to select the desired alarm tone Table 8 Switch Settings Tone POS POS POS 2 3 4 Horn 1...

Page 6: ...m wiring MAXIMUM NUMBER OF CONDUCTORS Figure A FLUSH 4 BOX 2 8 32x1 SCREWS 4 SQ X 2 1 8 DEEP BACKBOX 4 SCREW COVERS 8 4 8 8 AWG 18 AWG 16 AWG 14 AWG 12 Figure B 8 8 8 8 AWG 18 AWG 16 AWG 14 AWG 12 MAXIMUM NUMBER OF CONDUCTORS 4 6 32x1 4 SCREW COVERS SCREWS FLUSH 2 GANG BOX 2 GANG x 3 1 2 DEEP BACKBOX Figure C 8 8 8 8 AWG 18 AWG 16 AWG 14 AWG 12 MAXIMUM NUMBER OF CONDUCTORS 2 WOOD 4 8 18x1 4 SCREW ...

Page 7: ...lso be mounted to a surface with the two mounting ears that are supplied The ears slide into slots on the back of the box Figure C Use appropriate anchors for the wood screws that are supplied with the box if necessary 6 The IOB includes a prefastened gasket and four hole plugs Make sure the condensation drain holes on the box face down and that the box is vertical to permit drainage of any moistu...

Page 8: ...d or audio circuits for example may require special precautions to assure electrical noise immunity e g audio crosstalk The Multitone Strobe products and these instructions are copyrighted by Wheelock and Multitone Strobe products contain proprietary confidential and trade secrets of Wheelock No part of the Multitone Strobe products and these instructions may be photocopied printed or reproduced i...

Page 9: ...ONDITIONS BEYOND MANUFACTURER S CONTROL SOME OF THE MANUFACTURER S PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS THE MANUFACTURER DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIREMENTS THE MANUFACTURER S...

Reviews: