FP2 Analog Unit
Specifications
14 - 14
14.4 Shared Memory for Analog Input Processing
14.4.3
Analog Input Range Setting (addresses 18 to 21)
When setting the input range independently for each input channel, after setting the
range setting switch to ”Enable setting by software,” the codes for the range settings
shown below are set to addresses 18 to 21.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Address 18
(Default: HFFFF)
Ch 0
Ch 1
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Address 19
(Default: HFFFF)
Ch 2
Ch 3
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Address 20
(Default: HFFFF)
Ch 4
Ch 5
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Address 21
(Default: HFFFF)
Ch 6
Ch 7
Bit position
Bit position
Bit position
Bit position
Input range
Code
±
10V (
±
20mA)
H01
±
100mV
H04
1 to 5V (4 to 20mA)
H07
Thermocouple J
H0D
Thermocouple K
H0E
Thermocouple R
H0F
Thermocouple S
H10
Thermocouple T
H11
R.T.D Pt100
H12
R.T.D Pt1000
H13
If a code different from those above are set (excluding HFF), the input range is set to
±
10V (
±
20mA). Also, if HFF is set, conversion will not be executed for that input channel.