FP2 Analog Unit
Setting the I/O Range and I/O Allocation
4 - 3
4.1
Setting the Input and Output Range
4.1
Setting the Input and Output Range
Set the analog input and output range using the range setting switch on back side of unit.
4.1.1
Setting the Analog Input Range
When setting the same range for the all the channels at once, you can only use the range
setting switch. Use 1 to 5 of the range setting switch for both the CPU unit with analog
I/O and analog input units. Use the table below as a base and set the range setting switch
for the input range you will use.
If you will be using different input ranges together, then set the range setting switch to
“Enable setting by software.” Also, for the analog input initial settings, you must set the
range for each unit by the sequence program.
For detailed information
section 5.1
+/-10V
+/-20mA
1 to 5V
4 to 20mA
+/-100mV
Thermocouple J
Thermocouple K
Thermocouple R
Thermocouple S
Thermocouple T
R.T.D (Pt100)
R.T.D (Pt1000)
Not used
Enable setting
by software
Note
Be sure that range setting switches No.6 to 8 are off before use. If
they are on, operation will not be normal.