FP2 Analog Unit
Functions and Restrictions
1 - 6
1.3
Data Processing Functions
1.3.2
Analog Output
For analog output, there is the “Analog output hold function.”
1.3.2.1
Analog Output Hold Function
Non-hold, hold (final value during RUN mode), and hold (any value) for the analog
output during the FP2 CPU unit PROG. mode can be set by the shared memory
settings.
For hold (final value during RUN mode), the analog output value is held corresponding
to the final digital data written during the RUN mode before changing to the FP2 CPU
unit PROG. mode.
For hold (any value), the analog output value is held corresponding to the hold data (any
value) set in the shared memory when changing to the FP2 CPU unit PROG. mode.
Note
When set to either hold (final value duringl RUN mode) or hold
(any value), the each analog output is held during stops in
operatiohn due to FP2 CPU unit hardware malfunctions or
operation delays.