FP2 Analog Unit
Analog I/O Conversion Characteristics and Conversion Cycle Time
6 - 3
6.1
Analog Input Conversion Characteristics
6.1
Analog Input Conversion Characteristics
The conversion characteristics of analog input range are shown below.
-10V to +10V DC
(K)
(V)
+32767
+16383
0
+5
+10
-5
-10
-16384
-32768
Input range -10V to +10V DC
V
K
-10
-32768
-7.5
-24576
-5
-16384
-2.5
-8192
0
0
2.5
8191
5
16383
7.5
24574
10
32767
If the input value exceeds the rated analog input range, the converted value becomes:
Input value
Converted value
-10V or less
-32768
+10V or more
+ 32767