FP2 Analog Unit
Specifications
14 - 3
14.1 Table of Performance Specifications
14.1 Table of Performance Specifications
14.1.1
General Specifications
Item
Specifications
Ambient temperature
0 to 55
°
C/32 to 131
°
F
Use the FP2 Analog output unit (FP2-DA4) within the ranges given below.
Output range
Ambient operating temperature
Current output range
(0 to 20mA)
Voltage output range
(
±
10V)
When using 4 channels: 0 to 45
°
C/32 to 113
°
F
When using 3 channels: 0 to 50
°
C/32 to 122
°
F
When using 1 or 2 channels: 0 to 55
°
C/32 to 131
°
F
When using 4 channels: 0 to 55
°
C/32 to 131
°
F
Storage temperature
-20 to +70
°
C/-4 to +158
°
F
Ambient humidity
30 to 85% RH (non-condensing)
Storage humidity
30 to 85% RH (non-condensing)
Breakdown voltage
D
500V AC, 1 minute between analog input terminal and analog output terminal for
FP2-C1A
D
500V AC, 1 minute between analog input/output terminal and ground
D
1500V AC, 1 minute between analog input/output terminal and AC external terminal
Insulation resistance
100M
Ω
or more (measured with a 500V DC megger testing)
- between analog input terminal and analog output terminal for FP2-C1A
- between analog input/output terminal and ground
- between analog input/output terminal and AC external terminal
Vibration resistance
10 to 55Hz, 1cycle/min: double amplitude of 0.75mm/0.030in., 10min. on X, Y and Z
directions
Shock resistance
98m/s
2
or more, 4 times on X, Y and Z directions
Noise immunity
1,500Vp-p with pulse widths 50ns and 1
µ
s
(based on in-house measurements)
Operating conditions
Free from corrosive gases and excessive dust
Weight
FP2-C1A: 260g/9.171oz
FP2-AD8: 160g/5.644oz
FP2-DA4: 160g/5.644oz
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]