FP2 Analog Unit
Specifications
14 - 9
14.3 Table of Shared Memory Area
D
Address 10 can only be written to after the first conversion is
complete when the power is turned on.
D
Addresses 18 to 21 can only be written to once using a user
program after RUN. Reading is possible all the time.
D
Regarding the preparation complete flag for analog input of
address 10, when switching from PROG.to RUN mode, the
preparation complete flags of all channels will turn on because
all channels are undergoing conversion execution. When the
non-execution setting for each channel is set, this is reflected
in the bit that corresponds to address 10.
When “Enable setting by software” is specified at the range
setting switch, the address 10 “analog input preparation
complete flag” will not turn on because conversion will not
take place until the range setting is performed.