FP2 Analog Unit
Troubleshooting
13 - 3
13.1 Problems Concerning the Analog Input
13.1 Problems Concerning the Analog Input
Problem
Remedy
Analog input conversion value cannot
be read.
Check the I/O allocation for the analog units.
Check the range settings.
Check the settings for no execution of conversion processing (shared
memory setting).
Check the analog signal wiring.
Proper current input conversion value
cannot be obtained.
Check the terminal block wiring.
Check the current input devices.
Conversion value is unsteady.
Make sure that you are using shielded twisted-pair wiring for the input
signal wires.
Make sure that the shielding of the shielded twisted-pair wiring is proper-
ly connected.
Make sure that no input signal wires are near other power wires.
Proper conversion value cannot be
obtained during R.T.D. Pt100
connection.
Check the range settings.
Check the three-wire wiring and restart the equipment.
Proper conversion value cannot be
obtained during thermocouple
connection.
Check the range settings.
Check the polarity of the thermocouple.