52
Operation Manual
FT1020G3 Rev 2.10.4
10
"SILENCE BUZZER"
The
buzzer
in FT1020G3 will sound for:
•
Fire alarm
(0.4 / 0.4 sec.)
•
Co-incidence alarm (2-zone or 2-unit dependent fire alarm): When only one zone or
one zone / address (alarm point) is in alarm status (0.8 / 5 sec.)
•
Pre-warning (0.8 / 5 sec.)
•
Quiet alarm (0.8 / 5 sec.)
•
Fault (continuous)
•
Disablements and Faults (1 sec. directly after the door to the FDCIE is closed.)
•
Activated interlocking input (0.8 / 0.8 sec.), if this option is selected via EBLWin.
•
Activated technical warning (0.5 / 10 sec.), if this option is selected via EBLWin.
•
Delayed alarm
Press "SILENCE BUZZER" button to silence the buzzer.
In case of a new alarm or if the push button "SILENCE BUZZER" is pressed again, the
buzzer will automatically re-sound.
10.1
Silence buzzer by open door
In EBLWin, the function "Silence Buzzer by Door Switch" can be selected. The buzzer will
then be disabled as long as the FT1020G3 cabinet door is open.
10.2
Silence buzzer by the "FB Bulgin Key"
Note:
Valid only for the New Zealand convention.
When the
New Zealand FB “Silence Alarms” Bulgin key switch
(outside switch) is
turned ON (i.e. “Silence Alarms” position) the buzzer is silenced until the Bulgin key is
turned to the “Normal” position.
If there is a fault or disablement whilst the door to FT1020G3 is closed, the FT1020G3
buzzer will sound continuously directly after the door is closed, the fault and disablement
messages will be shown in the display.
Note:
In the New Zealand convention, if any of the outputs for routing equipment ("Fire
Brigade TX" and "Fault TX") or outputs for alarm devices is disabled when the door of
FT1020G3 is being closed, the buzzer will sound continuously immediately after the door
is closed.
"
Alarm routing equipment left isolated
"
,
"
Fault routing
equipment left isolated
"
and
"
Silence switch left active
"
will be shown in
the LCD. This information has higher priority than the normal fault messages and
disablements.
25
Incl. Heavy smoke/heat alarm, AA alarm and Acknowledged alarm (New Zealand only).
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...