88
Operation Manual
FT1020G3 Rev 2.10.4
•
In EBLWin, create the SSD only for the Control Units that should be connected
during the installation time. Do not download the SSD until the TLON Network
installation is ready.
•
Always wait to download the SSD until the TLON Network installation is ready.
Later
, when one or more Control Units required to be added to the TLON Network:
•
Open the project in TLON Manager, add the new Control Unit(s) and install
(download) it according to the separate TLON Manual MA437.
•
Open the SSD in EBLWin, add the Control Unit(s) and download the SSD to all
Control Units.
18.3.2
TLON Network Installation (Single)
•
Create a project in the PC program TLON Manager.
•
Connect your PC to the modular connector "J10" (Network no. 0) in a control unit.
Open the project in TLON Manager and install (download) the project.
For more information see Technical / Operation Manual M437.
18.3.3
TLON Network Installation (Redundant)
In a redundant network,
two Projects
must be created and installed. The Projects have to
be identical but with different Project names. One project has to be installed for Network
no. 0 and another project to be installed for Network no. 1.
In a redundant TLON system, connect your PC to the modular connector "J10" to download
the TLON configuration for Network no. 0 then connected to J11 to download Network no.
1 configuration.
Note:
After the TLON Network installation is completed (downloaded), it is highly
recommended to restart the Control Units.
18.3.4
Add a Control Unit into a TLON Network
When adding a new Control Unit to an "existing" system, the same system software (S/W)
version must be used in all Control Units. Often the new Control Unit has a newer version
than the existing Control Units. Normally the latest version is recommended to be used, i.e.
the Control Units in the "existing" system have to be upgraded. As an alternative, it may
possible to download an earlier S/W version in the new Control Unit.
Important Note
: When the control unit is supplied with main board 5012 or MMI 5015
board, the lowest S/W version is 2.10.4.
Both options are described in chapter "Download Software (System Firmware)", page 102.
The following procedures to be followed to add a new Control Unit to an existing system:
1.
Open the current project in
TLON Manager.
2. Add one Control Unit and install (download) as shown in section 18.3.3 above,
refer to the TLON technical manual for more details.
3. Open the SSD for the current system in EBLWin. Add one Control Unit (and the
units connected to it).
4. Download the new SSD according to chapter "Software Installation and SSD
18.3.5
Merge Two TLON Networks
1. Ensure the system properties identical in the two systems.
2. Ensure that no presentation numbers in the network system are the same.
3. Select one of the systems as the starting point, for example the largest system,
and add the control units and all other units from the other system.
Note
: Two or more presentation numbers (Zone or Zone-Address) in the systems must not
be the same.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...