104
Operation Manual
FT1020G3 Rev 2.10.4
After the restart, the following fault messages will be shown:
Code 00 / 50 indicates a normal restart of the main board / MMI board after the software
download. Acknowledge the restart faults.
13. Acknowledge the restart faults, LED “Operation” on the FT1020G3 front should
now be turned on and all other LEDs should normally be turned off.
New SSD can now be downloaded.
Note
: After a new software download, the logon password reverts back to the default
setting i.e. “000000”. The user names and passwords will be changed when the SSD is
downloaded.
20.2
Download Software in a TLON Network
All Control Units connected to a TLON network
must
have the same software version.
Also, in a network system, the system software is downloaded separately to every FDCIE.
Before upgrading the software in a TLON network, it is recommended to disconnect the
control units from the network. It can be carried out physically (disconnect the TLON cable
from the FDCIE), or via TLON Manager.
Note 1
: It is highly recommended to disconnect the TLON network during upgrade in large
networks. Otherwise, it will result in large amount of fault messages.
Note 2
: The TLON PCBs must remain mounted in the control units, or the control units will
lose their TLON configuration.
To download new software in each Control Unit, follow the procedures below:
1. Disconnect the webserver, RS232 in the FDCIE (if any).
2. Open TLON manager in your PC. Connect the FT1020G3 System to TLON
Manager and set all control units to “Offline”.
3.
Follow the procedure 1 to 13 in section
page 102
4. One by one, as the control units start up after download, they will automatically
get “online” in TLON Manager, and the communication will start to run as
normal.
5. Download compatible software in the webserver or gateway via TCP/IP (if any).
6. Download SSD to the control units, follow the procedures shown in
page 99. In large systems, it is preferable to download SSD
to one control unit at a time. This is to avoid a large amount of traffic on
the TLON network.
FAULT: Restart control unit nn, code 00
DD-MM-YYYY HH:MM
FAULT: Restart control unit nn, code 50
DD-MM-YYYY HH:MM
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...