165
Operation Manual
FT1020G3 Rev 2.10.4
30.2
Activate / Deactivate Interlocking Output (H9/C2)
The output in each interlocking combination (area / point) can be manually activated via
this menu. The corresponding interlocking input will be "monitored" in the same way as if
the output was activated by its control expression.
The output in each interlocking combination (area / point) can be manually deactivated via
this menu.
Note:
The output will be deactivated if its control expression still true and can’t be activated
again until the control expression has been false. Also, a latched output will be deactivated.
If an interlocking output is activated via its control expression and with latching output
selected (in EBLWin), the output must be deactivated via this menu.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H9.
H9 Interlocking outputs and inputs
"
↲
"
C1 Activated interlocking outputs / inputs
C2 Activate / deactivate interlocking output
C3 Disable / re-enable interlocking output
Scroll to menu C2.
C2 Activate / deactivate interlocking output
"
↲
"
Activate
Interlocking output area:
0
00 point: 00
Write area number and
address and press "
↲
"
to activate, which will be
indicated with "
√
" and a
beep. The output will
directly be shown in the
Deactivate list.
Write the area number
and point (e.eg. 001
and 01.
"
↲
"
Activate
Interlocking output area: 001 point: 01
√
-- Deactivate list (1) ---------------------------------------------
Interlocking output area: 001 point: 01
If the specified output
doesn't exist, it will be
indicated with "X"
instead of "
√
" and a
beep.
Use the soft key "
|
" to
toggle between
Activate
and
Deactivate
list
.
"
|
"
-- Activate ----------------------------------------------------------
Interlocking output area: _ _ _ point: _ _
Deactivate list (1)
Interlocking output area: 001 point: 01
Select in the Deactivate
list with "▼" (in this
example there is only
one output) and press
"
↲
".
The deactivated output
will disappear from the
list, indicated with a
beep.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...