Installation and user manual for the

FX range of fire panels

1, 2, 4 and 8 zone panels

Summary of Contents for FX range

Page 1: ...Installation and user manual for the FX range of fire panels 1 2 4 and 8 zone panels...

Page 2: ...el installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check 8 Commissioning User information Maintenance Tables Sounder and Visual Indication 9 Technical S...

Page 3: ...m Within the panel the mains supply should be isolated from the zone and alarm line wiring and should be connected to the terminal block marked MAINS Battery connection The 1 2 4 zone panel requires a...

Page 4: ...oved This range of control panels can support up to 32 detectors max per zone and an unlimited number of call points per zone Sounder wiring The standard 1 2 and 4 zone fire alarm control panels have...

Page 5: ...2 then silence then reset check all indicators show momentarily Check each zone and alarm line for open and short circuit fault monitoring Zone circuits Disconnect the mains and battery supply wire in...

Page 6: ...s the panel indicators and resets faults relay access code level 2 There are 2 access codes used by the control panel access level 2 client code 3112 and access level 3 engineers code These codes are...

Page 7: ...l times until sounder LED turns off Push button to confirm enable sounders 3 1 2 5 Disable zone Isolates required detection zone from the system access code level 2 3 1 2 5 1 2 3 4 5 1 2 3 4 5 Detecto...

Page 8: ...ad by activating a call point Log test results in log book Six monthly Test As per quarterly test Visual inspection of site to check for compliance of system to recommendations of local standard The t...

Page 9: ...el type 1 Zone 2 Zone 4 Zone 8 Zone Detection zones 1 2 4 8 Detectors per zone 32 Alarm lines 2 4 Max alarm line load 300mA total shared 800mA total shared 500mA per alarm line 2A total Fire Fault rel...

Page 10: ...PINSTFX2200GENR1 PR000 00 513 01...