Please read the following instructions before installing and wiring
the fire alarm panel.

This range of panels are EN54 parts 2 and 4 certified and have
been designed to comply with BS5839 part 1:2002 installations.
The panels have two optional features:-
FIRE ALARM DEVICES: (EN54 part 2 clause 7.8)
TEST CONDITION: (EN54 part 2 clause 10.0)

In common with all electrical equipment the panel should be
installed in a clean, dry, well ventilated area, not in direct sun light
and avoiding cold areas where possible. Note, temperatures in
excess of 40°C will affect the panel operation. The panel should
be located away from any potential hazard, in a position where it
is readily accessible to authorised staff and the fire services.
Ideally on the perimeter of a building near a permanent entrance.

Mains power supply

The mains supply should be exclusive to the fire alarm as
detailed in BS5839 part 1. It is recommended that a double pole
fused spur unit is used and marked “FIRE ALARM DO NOT
SWITCH OFF”, this should be for the sole use of the fire alarm.
Within the panel, the mains supply should be isolated from the
zone and alarm line wiring and should be connected to the
terminal block marked MAINS.

Battery connection

The 1, 2 & 4 zone panel requires a single battery (supplied):

1 zone panel:

1x12V 2.1Ah.

2 and 4 zone panels:

1x12v 3.2Ah

Connect the red battery wire to the red battery terminal (+).
Connect the black battery wire to the black battery terminal (-).

The 8 zone panel requires two batteries (supplied):

2x12v 3.2Ah

Connect the red battery wire to the red battery terminal (+) of
battery one.
Connect the black battery wire to the black battery terminal (-) of
battery two then connect the link cable as shown below.

Mount the panel, using pre drilled screw positions, to the wall.
This will prevent any possible brick dust contamination of the
panel internal circuitry.
When using 20mm conduit entry direct to the top of the
housing, use a coupler to ensure a wide distribution of pressure
when tightening the coupling.

Wiring

The following cable type and size are recommended:
Mains wiring:- 1.5mm

2

, 2 core, fireproof cable

Zone wiring:- 1.5mm

2

, 2 core, fireproof cable

Sounder wiring:- 1.5mm

2

to 2.5mm

2

, 2 core, fireproof cable

WARNING

DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS
CONNECTED TO ANY ELECTRONIC EQUIPMENT

230 VAC

L

Black -

Red +

N

Summary of Contents for FX range

Page 1: ...Installation and user manual for the FX range of fire panels 1 2 4 and 8 zone panels...

Page 2: ...el installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check 8 Commissioning User information Maintenance Tables Sounder and Visual Indication 9 Technical S...

Page 3: ...m Within the panel the mains supply should be isolated from the zone and alarm line wiring and should be connected to the terminal block marked MAINS Battery connection The 1 2 4 zone panel requires a...

Page 4: ...oved This range of control panels can support up to 32 detectors max per zone and an unlimited number of call points per zone Sounder wiring The standard 1 2 and 4 zone fire alarm control panels have...

Page 5: ...2 then silence then reset check all indicators show momentarily Check each zone and alarm line for open and short circuit fault monitoring Zone circuits Disconnect the mains and battery supply wire in...

Page 6: ...s the panel indicators and resets faults relay access code level 2 There are 2 access codes used by the control panel access level 2 client code 3112 and access level 3 engineers code These codes are...

Page 7: ...l times until sounder LED turns off Push button to confirm enable sounders 3 1 2 5 Disable zone Isolates required detection zone from the system access code level 2 3 1 2 5 1 2 3 4 5 1 2 3 4 5 Detecto...

Page 8: ...ad by activating a call point Log test results in log book Six monthly Test As per quarterly test Visual inspection of site to check for compliance of system to recommendations of local standard The t...

Page 9: ...el type 1 Zone 2 Zone 4 Zone 8 Zone Detection zones 1 2 4 8 Detectors per zone 32 Alarm lines 2 4 Max alarm line load 300mA total shared 800mA total shared 500mA per alarm line 2A total Fire Fault rel...

Page 10: ...PINSTFX2200GENR1 PR000 00 513 01...

Reviews: