Commissioning the system

User information

6

Assuming that the installation instructions and installation checks
have been carried out successfully the fire alarm system is ready
for commissioning.
Each detector and call point should be tested in turn to ensure
that it operates, indicates the correct zone fire LED and operates
the alarm output correctly, ensuring all sounders/bells operate.

Walk test facility

A walk test function has been included in this range of panels to
enable one person (electrical contractor or installer) to test the
fire detection system without an assistant. This function is for the
sole use of the electrical contractor or installer and not for normal
operational use.

Silence alarm

Silences external sounders and mutes internal buzzer

Access code level 2 + 

Evacuate

Operates the control panel’s sounder circuits and fire relay(s)

access code level 2 + 

Reset after fire alarm activation

Silences buzzer, resets the panel indicators, resets detectors and
resets control relays

access code level 2 + 

Ensure any smoke still in the activated detector is blown clear,
as the control panel will activate back into alarm should any
smoke remain.

Reset panel without a fire activation

(e.g. to reset a fault indication when fault latch facility set)
Silences buzzer, resets the panel indicators and resets faults
relay

access code level 2 + 

There are 2 access codes used by the control panel: -
access level 2 - client code (3112)

and 

access level 3 - engineers code 

These codes are displayed on the rear of the front panel.
The access level 2 code is also shown on the panel key fob.

Level 2 access permits the following functions:
- Silence alarm
- Evacuate
- Enable and disable zones
- Enable or disable sounders
- System reset
The access code (level 2 or 3) is enabled by pressing the five
control panel front buttons in the correct sequence.

   

An audible signal indicates that the access code keyed in is
correct.

Mute buzzer

Silences control panel’s internal buzzer

access code level 2 + 

The walk test facility access code is located inside the fire
detection control panel.
Once the walk test code has been correctly entered the ‘test in
progress’ indicator will show and the buzzer will pulse, this sets
a time window of 10 minutes.
If a detector or call point is triggered within this period the
sounders will operate for a short time then the system will
automatically reset ready for the next call point or detector
activation.
If a detector or call point is not operated within the 10 minute
period then the system will automatically reset and return to
normal operation.
The walk test facility can be terminated at any time during test
by pressing the ‘reset’ button.

1

2

3

4

5

2

3

4

1

2

4

5

To silence the alarm during evacuate period

access code level 2 + 

3

4

5

3

4

5

3

4

5

Summary of Contents for FX range

Page 1: ...Installation and user manual for the FX range of fire panels 1 2 4 and 8 zone panels...

Page 2: ...el installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check 8 Commissioning User information Maintenance Tables Sounder and Visual Indication 9 Technical S...

Page 3: ...m Within the panel the mains supply should be isolated from the zone and alarm line wiring and should be connected to the terminal block marked MAINS Battery connection The 1 2 4 zone panel requires a...

Page 4: ...oved This range of control panels can support up to 32 detectors max per zone and an unlimited number of call points per zone Sounder wiring The standard 1 2 and 4 zone fire alarm control panels have...

Page 5: ...2 then silence then reset check all indicators show momentarily Check each zone and alarm line for open and short circuit fault monitoring Zone circuits Disconnect the mains and battery supply wire in...

Page 6: ...s the panel indicators and resets faults relay access code level 2 There are 2 access codes used by the control panel access level 2 client code 3112 and access level 3 engineers code These codes are...

Page 7: ...l times until sounder LED turns off Push button to confirm enable sounders 3 1 2 5 Disable zone Isolates required detection zone from the system access code level 2 3 1 2 5 1 2 3 4 5 1 2 3 4 5 Detecto...

Page 8: ...ad by activating a call point Log test results in log book Six monthly Test As per quarterly test Visual inspection of site to check for compliance of system to recommendations of local standard The t...

Page 9: ...el type 1 Zone 2 Zone 4 Zone 8 Zone Detection zones 1 2 4 8 Detectors per zone 32 Alarm lines 2 4 Max alarm line load 300mA total shared 800mA total shared 500mA per alarm line 2A total Fire Fault rel...

Page 10: ...PINSTFX2200GENR1 PR000 00 513 01...

Reviews: