The yellow LED of the zone 1 will light and the internal buzzer will

pulse rapidly, push button 

several times until both the required

zone and disabled yellow LED’s are lit.

Push button 

to disable the indicated zone.

Repeat this procedure to disable further zones.
The internal buzzer will pulse at a slow rate and the disabled
and zone disabled LED’s will remain lit.
To silence the internal buzzer

access code level 2 + 

The yellow LED of the zone 1 will light and the internal buzzer will

pulse rapidly, push button 

several times until both the disabled

and sounders disabled yellow LED’s are lit.

Push button 

to confirm disable sounders.

The internal buzzer will pulse at a slow rate and the disabled and
sounders disabled LED’s will remain lit.
To silence the internal buzzer

access code level 2 + 

Enable zone

access code level 2 + 

Yellow led of the first zone is flashing. Push button 

several

times until the yellow led of the relevant zone is flashing.

Push button 

to enable the relevant zone.

Repeat this procedure to enable further disabled zones.

3

1

2

5

Disable sounders

Isolates sounder circuits from the system

access code level 2 + 

3

1

2

5

Enable sounders

access code level 2 + 

Internal buzzer will rapidly pulse. Push button 

 

several times

until sounder LED turns off.

Push button 

 

to confirm enable sounders

3

1

2

5

Disable zone

Isolates required detection zone from the system

access code level 2 + 

3

1

2

5

1

2

3

4

5

1

2

3

4

5

Detector LED function (applies to self check detectors
only)

Self check detectors incorporate self check intelligence enabling
them to monitor their own status and to generate a fault signal at
the panel in the event of a malfunction.

Should a detector develop a fault, the zone to which the detector
is connected will indicate a zone fault and the status LED on the
faulty detector will illuminate amber.

Should the detector fail completely, it is possible to instruct the
panel to illuminate the LED's of the healthy indicators instead.

To activate this function, 

enter the ENGINEERING code 3421 at

the control panel then PRESS 3.........

To cancel this mode, 

ENTER THE ENGINEERING CODE 3421 AT

THE CONTROL PANEL AND THEN PRESS 3..........

The LED control facility can also be used to diagnose faults in the
external zone wiring, should a zone open circuit occur, activate
the LED test mode as described above, the LED's of all detectors
which still have a healthy connection to the panel will flash,
greatly simplifying the location of the break.

Follow the instructions above to cancel LED indicator mode.

Self check detectors

To activate this function,

access code level 3 (engineer’s code) + 

To cancel this mode,

access code level 3 (engineer’s code) + 

1

2

4

5

1

2

4

5

Summary of Contents for FX range

Page 1: ...Installation and user manual for the FX range of fire panels 1 2 4 and 8 zone panels...

Page 2: ...el installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check 8 Commissioning User information Maintenance Tables Sounder and Visual Indication 9 Technical S...

Page 3: ...m Within the panel the mains supply should be isolated from the zone and alarm line wiring and should be connected to the terminal block marked MAINS Battery connection The 1 2 4 zone panel requires a...

Page 4: ...oved This range of control panels can support up to 32 detectors max per zone and an unlimited number of call points per zone Sounder wiring The standard 1 2 and 4 zone fire alarm control panels have...

Page 5: ...2 then silence then reset check all indicators show momentarily Check each zone and alarm line for open and short circuit fault monitoring Zone circuits Disconnect the mains and battery supply wire in...

Page 6: ...s the panel indicators and resets faults relay access code level 2 There are 2 access codes used by the control panel access level 2 client code 3112 and access level 3 engineers code These codes are...

Page 7: ...l times until sounder LED turns off Push button to confirm enable sounders 3 1 2 5 Disable zone Isolates required detection zone from the system access code level 2 3 1 2 5 1 2 3 4 5 1 2 3 4 5 Detecto...

Page 8: ...ad by activating a call point Log test results in log book Six monthly Test As per quarterly test Visual inspection of site to check for compliance of system to recommendations of local standard The t...

Page 9: ...el type 1 Zone 2 Zone 4 Zone 8 Zone Detection zones 1 2 4 8 Detectors per zone 32 Alarm lines 2 4 Max alarm line load 300mA total shared 800mA total shared 500mA per alarm line 2A total Fire Fault rel...

Page 10: ...PINSTFX2200GENR1 PR000 00 513 01...

Reviews: