16
Operation Manual
FT1020G3 Rev 2.10.4
3.2
FT1020G3 Limitations
Some limitations have been increased as well as adding new types. The following table
lists some of the limitations in V2.10.x software.
Table 3 Control Unit limitations
Item
Loop FDCIE Network System
General fire alarm via programmable input
100
30 x 100
External fault via programmable input
100
30 x 50
Programmable inputs
512
30 x 512
Programmable outputs (= control expressions)
512
30 x 512
Technical warnings
200
30 x 100
Addressable 2 voltage outputs unit 3364
40
30 x 40
Interlocking Combinations
400
4000
Presentation numbers / alarm points that can be presented
in the display(s) in case of fire alarm
255
512
512
Presentation numbers that can be programmed
512
30 x 512 = 15 360
Zones that can be programmed
255
512
999
Zone Group
64
64
Faults
300
Disabled Zones
512
Disabled Alarm Points (zone/address) + Disabled COM loops
200
Disabled Outputs
200
Disabled Interlocking Outputs
200
Sensors activating SERVICE signal
200
LAA zones (Max. 5 detectors per AAF zone.)
100
30 x 100
Total number of Expansion Boards 4580 and 4581
6
30 x 6
Number of I/O Matrix Boards 4582
24
30 x 24
Total number of 4582 for Zone Control & Generic applications
6
30 x 6
Maximum number of remote display units 5054 (1728 / 1736)
30
30 x 30
Maximum number of 19” rack fan/damper modules with built-
in 4582 (4 fan/damper for each module)
24
30 x 24
Maximum number of 19” rack zone modules with built-in 4582
(15 zone)
6
30 x 6
Note
: The addresses 254 and 255 in each loop are reserved for auto addressing purposes and
cannot be used. If these addresses are used there will be a fault in the "Validity check".
6
Zone/address disabled via time channel not included.
7
Control outputs disabled via menu H2/B3 and Alarm devices disabled via menu H2/B4 are not included.
8
Expansion boards 4580 and 4581 are physical connected to COM loop 0
9
Reduce no. of 4582 boards by one for every Expansion Board used (4580 or 4581), applicable to 19” rack
modules for zone control and fan / damper control.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...