Operation Manual
FT1020G3 Rev 2.10.4
4.4
Gaseous Extinguishing Control Module
The gaseous extinguishing control module is available to use as an option in FT1020G3.
The gas module provides outputs to drive the following:
•
A combination of Brooks Warning Signs
•
Brooks Local Control Station (LCS)
•
Voice / Tone Electronic Sounder
•
Dual Strobe Module
The gas control module combined with other Brooks system components has been
designed to provide monitoring and control functions of a complete gaseous extinguishing
system that conforms to the requirements of the relevant clauses 7.1 to 7.6 of the Australian
Standard AS4214-2002 (including amendment 1). For more details, refer to FT2GAS
Operation / Technical Manual MA400.
The gaseous extinguishing front display is shown in Figure 5. All LED indicators on the
front display are covered by a polycarbonate decal clearly labelled with their functions.
When the system is in normal condition, all LED indicators will be extinguished.
Figure 5 Gas Extinguishing Display Layout
The gaseous extinguishing system status LEDs and flash patterns are described in Table 11
below be. The default state of the LED indicators is OFF, if it is not defined in the table.
Table 11 Gas Front Status LED Indication and flash Pattern
Type
LED Name
Module Conditions
LED
Pattern
Alarm
1st Alarm - Red
One zone or zone address in alarm
Fast Flash
2nd Alarm – Red, Timer
Running
Both zones or zone addresses in alarm
Gas Initiated - Red
Gas release output activated
Gas Externally Released - Red External gas release control activated
Gas Discharged - Blue
Gas discharged sensor input activated
Fault
Gas Fault - Yellow
Fault in any of the supervised inputs or
outputs
Steady ON
Disable
Gas Discharge Inhibited -
Yellow
Gas discharge inhibited via LCS isolate switch
Steady ON
Gas Discharge Disabled -
Yellow
Gas discharge disabled by the service master
abort switch or the gas lock-off valve controls
Service Switch Active - Yellow Illuminates when the master abort switch
is activated
Service, Master Abort
Gas service master abort switch
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...