38
Operation Manual
FT1020G3 Rev 2.10.4
1207
1208
1209 1210
Figure 16 Display and control modules
5.5.1
Generic 8 Switches / 8 LED’s Display / Control Module 1207
1207
is a Generic
8 programmable switches
and
8 programmable LEDs
display and
control module, programmed as a normal type input (switch) and a normal type output
(LED).
The module requires
two
COM loop addresses and one 10HP (50 mm) space on the
ancillary 19” rack, the second address is automatically allocated. Can connect to any COM
loop 0-3, limitation is dependent on max. loop current consumption. DIP switch is provided to
change the LED’s colour (green, red or amber), refer to the technical datasheet TDS059
for colour setting.
Each switch input can be configured to be latched (toggle) or non-latched (momentarily)
and each LED output can be interlocked with the switch input i.e. follow the switch activation
or can be activated independently by an output logical expression.
Address setting tool 4414E is used to address 1207 in
Advanced mode (3)
.
5.5.2
Generic 4 Switches / 8 LED’s Display / Control Module 1208
1208 is a
Generic
4 switches
and
8 LEDs
display and control module. The functionality
and programmability of the switch input and led output are identical to 1207 except the
number of switches is 4. 1208 is programmed as a normal type input (switch) and a normal
type output (LED).
The module requires
two
COM loop addresses and one 10HP (50 mm) space on the
ancillary rack. The second address is automatically allocated. Can connect to any COM loop
0-3, limitation is dependent on the max. loop current consumption. DIP switch is provided to
change the LED’s colour.
Address setting tool 4414E is used to address 1208 in
Advanced mode (3)
5.5.3
Generic 8 LED’s Display Module 1209
1209 -
Generic
8 LEDs
display module, programmed as a normal type output (LED). The
module requires
one
COM loop address and one 10HP (50 mm) space on the ancillary
rack. Can connect to any COM loop 0-3. DIP switch is provided to change the LED’s colour.
Address setting tool 4414E is used to address 1209 in
Advanced mode (3)
5.5.4
Pump status 6 LED’s Display Module 1210
1210
–
6 LEDs
Pump Status Monitor, specialised module to monitor the status of pumps
or monitor water tank high / low. Requires
one
COM loop address and one 10HP (50 mm)
space on the ancillary rack. DIP switch settings can be used to change the LED display
colours. Address setting tool 4414E is used to address 1210 in
Advanced mode (3)
Please refer to The Technical Datasheet TDS059 for full details on DIP switch settings,
programming, and installation.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...