167
Operation Manual
FT1020G3 Rev 2.10.4
30.3
Disable / re-enable interlocking output (H9/C3)
Interlocking outputs (Type = Interlocking) can be individually disabled via this menu (and
collectively via menu H2/B3). The "Interlocking Combination" (Area / Point) is to be entered
to disable the output. Up to 100 interlocking outputs can be disabled in the whole system.
Disabled interlocking outputs are listed in menu H4/U1.
The LED Fault / Disablements "General disablements" (L10) is also indicating one or more
disabled interlocking outputs.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 42.
Scroll to menu H9.
H9 Interlocking outputs and inputs
"
↲
"
C1 Activated interlocking outputs / inputs
C2 Activate / deactivate interlocking output
C3 Disable / re-enable interlocking output
Scroll to menu
C3
C3 Disable / re-enable interlocking output
Interlocking outputs can
be disabled / re-enabled
via menu C3.
"
↲
"
Disable
Interlocking output area:
0
00 point: 00
Write area number and
address and press "
↲
" to
disable, which will be
indicated with "
√
" and a
beep. The output will be
automatically shown in
the Re-enable list.
Write the area number
and point (e.g. 001
and 01).
"
↲
"
Disable
Interlocking output area: 001 point: 01
√
-- Re-enable list (1) ---------------------------------------------
Interlocking output area: 001 point: 01
If the specified output
doesn't exist, it will be
indicated with "X"
instead of "
√
" and a
beep.
Use the soft key "
|
" to
toggle between
Disable
and
Re-enable
list
.
"
|
"
-- Disable -----------------------------------------------------------
Interlocking output area: _ _ _ point: _ _
Re-enable list (1)
Interlocking output area: 001 point: 01
Select in the Re-enable
list with "▼" (in this
example there is only
one output) and press
"
↲
".
The re-enabled output
will disappear from the
list, indicated with a
beep.
"
↲
"
Disable
Interlocking output area:
0
00 point: 00
Continue as above or
press "ESC".
"ESC"
C3 Disable / re-enable interlocking output
Scroll to another menu
or press "ESC".
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...