157
Operation Manual
FT1020G3 Rev 2.10.4
Power off / Power on
or
after 5 min.
FAULT: Restart control unit 00, code 53,
address 0
dd-mm-yyyy hh:mm
/Serviced
FAULT: Restart control unit 00, code 03,
address 0
dd-mm-yyyy hh:mm
/Serviced
Fault 1/2 is selected
After a restart (see page
107) two restart faults
will be always exist.
The code will be 00 / 50
after Power off / Power
on restart and 03 / 53
after a countdown
restart, address 0. This
fault has to be
acknowledged, see
chapter "
Previous
page
Next
page
Code 50 and 53 respectively will only appear if the control unit has an MMI board.
Note:
Prior the very first
safe shut down,
the Flash ROM is empty. Then every time
safe
shut down
is performed the valid data will be saved in the Flash ROM, i.e. some of the old
data will be overwritten. When the FDCIE is powered up, the data stored in the Flash ROM
will be used.
WARNING
: If
safe shut down
is
not
performed just before the FDCIE power down, then
when powered on, the Flash ROM may be empty i.e. default setting will be used or the
stored data may be old / not valid.