107
Operation Manual
FT1020G3 Rev 2.10.4
21
Restart
A restart may delete some data in FT1020G3. Below follows an explanation of the different
data and abbreviations and a table describing the different reset alternatives and how the
data respectively is affected (
cold
or
warm restart
).
FF
=
F
ire alarms and
F
aults.
D
=
D
isablements
FFD
=
F
ire alarms,
F
aults and
D
isablements.
SSW
= Sensor min. / max. values & performance factor, supervised output calibration
values and event logs.
WASV
=
W
eek
A
verage
S
ensor
V
alues
SSD
=
S
ite
S
pecific
D
ata, i.e. all the installation programming created and
downloaded via EBLWin.
S/W
= Software, i.e. the EBL512 G3 system program.
The date & time and alarm counter value is stored in the memory of the real time clock, i.e.
the value will be retained also after the FDCIE has been powered down.
Note
: After any restart, a new week average sensor value will be calculated within two
minutes for all the analogue smoke detectors. During these two minutes all fire alarms from
analogue smoke sensors will be suppressed. Thereafter a new average sensor value will
be calculated each week
21.1
Safe Shut Down
Safe shut down of Control Unit
via menu
H8/S6
will save the
SSW
data in a Flash ROM
in FT1020G3. Before the first "Safe shut down" of the Control Unit, this memory is empty.
After each "Safe shut down" the latest
SSW
data is saved (Safe shut down will not save
the week average sensor values).
When FT1020G3 is powered up, a restart takes place and the RAM (working memory) will
read the
SSW
data saved in the Flash ROM.
21.2
Restart Table
Table 18 below describes the different reset alternatives and how the data is affected.
Table 18 Data affected by restart
Action
Data Deleted Data not Deleted Restart
Code
Power down and then power up again. (both
mains and batteries disconnected)
SSW, FFD,
WASV
SSD, S/W, SSW
Passwords
00 (+ 50)
Via menu H8/S5 Safe shut down of Control Unit. FFD, WASV SSD, S/W, SSW
00 (+50)
03 ( +53)
Via RESET button on Main board 5012. If this
reset is done in the middle of a process,
also the SSW might be deleted.
FFD, WASV SSD, S/W, SSW
03
Via RESET button on MMI board
SSD, S/W, SSW
FFD, WASV
53
Reset command via EBLWin or TLON
Manager.
FFD, WASV SSD, S/W, SSW
03 (+53)
Automatically after download of Site Specific
Data (SSD) via EBLWin.
FFD, WASV SSD, S/W, SSW
25
Automatically after download of S/W via
EBLWin.
The old S/W will be deleted.
FFD, WASV,
passwords
SSD, S/W, SSW
00 (+50)
Automatically due to trying to use auto boot
mode with a MMI board that doesn’t support auto
boot mode
FFD, WASV SSD, S/W, SSW
15
39
SSW previously saved with safe shut down is not deleted.
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...