70
Operation Manual
FT1020G3 Rev 2.10.4
16.9
Alarm Delay Facility (ADF) Reset
The ADF alarm will be automatically reset if the smoke clears during acknowledgement or
investigation time delay i.e. the device is no longer in alarm condition when the delay time
elapsed. Refer to section 15.7.2 page 64.
16.10 Local Alarm Acknowledgement (LAA) Reset
The indication in the Control Unit display, during the Acknowledgement Period (10-120
sec.) and the Investigation Period (1-9 min.) respectively, will automatically clear when:
•
The AA process is terminated because no detector in the LAA zone is over the fire
alarm level.
•
The AA process ends up in a fire alarm, which has higher priority.
16.11 Quiet Alarm Reset
Quiet alarms are non-latching, i.e. they will be automatically reset when the alarm point /
zone is no longer in alarm state. Outputs activated by quiet alarm will be de-activated (in
some cases after a programmable delay time).
Summary of Contents for Firetracker FT1020G3 CIE
Page 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Page 2: ...This page has deliberately been left blank...
Page 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Page 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...