42
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
43
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
Split Systems with Hydro-Module / LT Series / H Generation (contd.)
LT series
Three-phase (400 V / 50 Hz), heating and cooling
Hydro-module
WH-SDC09H3E8
WH-SDC12H9E8
WH-SDC16H9E8
Outdoor unit
WH-UD09HE8
WH-UD12HE8
WH-UD16HE8
Set (hydro- outdoor unit)
KIT-WC09H3E8
KIT-WC12H9E8
KIT-WC16H9E8
Model
B6
B6
B6
Heating capacity at +7 °C (A7/W35)
kW
9.00
12.00
16.00
COP at +7 °C (A7/W35)
4.84
4.14
4.28
Heating capacity at +2 °C (A2/W35)
kW
9.00
11.40
13.00
COP at +2 °C (A2/W35)
3.59
3.44
3.28
Heating capacity at -7 °C (A–7/W35)
kW
9.00
10.00
11.40
COP at -7 °C (A–7/W35)
2.85
2.73
2.68
Cooling capacity at 35 °C (A35/W7)
kW
7.00
10.00
12.20
EER at 35 °C (A35/W7)
3.17
2.81
2.56
Energy efficiency class
1
at 35 / 55 °C
i
/
i
i
/
i
i
/
i
Hydro-module
Sound pressure level
Heating / Cooling
dB(A)
28 / 28
28 / 28
28 / 28
Dimensions
H x L x W
mm
892 x 500 x 340
892 x 500 x 340
892 x 500 x 340
Weight
kg
44
44
44
Water-side connection
mm
28
28
28
High efficiency pump
Rotation speed stages
Variable
Variable
Variable
Power consumption (min./ max.)
W
32 / 102
34 / 110
30 / 105
Water flow rate (A7/W35)
l/min
25.8
34.4
45,9
Power of E-heating element
kW
3
3
3
Power consumption
Heating / Cooling
kW
1.86 / 2.21
2.53 / 3.51
3.07 / 4.36
Operating and start up current Heating / Cooling
A
2.8 / 3.4
3.8 / 5.3
4.7 / 6.5
Max. power consumption on network connection 1 / 2
A
11.8 / 13.0
8.8 / 13.0
9.4 / 13.0
Recommended fuse for network connection 1 / 2
A
15 / 30
15 / 30
15 / 30
Recommended cable cross section for network connection 1 / 2 mm²
3 x 1.5 / 3 x 1.5
3 x 1.5 / 3 x 1.5
3 x 1.5 / 3 x 1.5
Outdoor unit
Sound pressure level
Heating / Cooling
dB(A)
51 / 49
52 / 50
55 / 54
Dimensions
H x L x W
mm
1,340 x 900 x 320
1,340 x 900 x 320
1,340 x 900 x 320
Weight
kg
108
108
108
Line diameter
Fluid line
mm (inches)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas line
mm (inches)
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
Pre-filled refrigerant (R410A) / CO
2
-equivalent
kg / t CO
2
-Equ. 2.55 / 5.324
2.55 / 5.324
2.55 / 5.324
Connection distance
m
3 – 30
3 – 30
3 – 30
Nominal connection distance
m
7
7
7
Pre-filled connection distance
m
10
10
10
Additional coolant fill-up quantity (R410A)
g/m
50
50
50
Max. height difference IU/OU
m
20
20
20
Operating range
Outside temperature (H / K)
°C
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
Water outlet temperature (H / K) °C
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efficiency classes is based on the official ErP specifications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been
in force since 26. September 2015. The efficiency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced starting in September 2019. Other ErP relevant
information is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Energy efficiency class scale from A++ to G.
Split systems with hydro-module / LT series / H Generation
LT series
Single-phase (230 V / 50 Hz), Heating and Cooling
Hydro-module
WH-SDC03H3E5-1
WH-SDC05H3E5-1
WH-SDC07H3E5-1
WH-SDC09H3E5-1
WH-SDC12H6E5
WH-SDC16H6E5
Outdoor unit
WH-UD03HE5-1
WH-UD05HE5-1
WH-UD07HE5-1
WH-UD09HE5-1
WH-UD12HE5
WH-UD16HE5
Set (hydro- outdoor unit)
KIT-WC03H3E5-1
KIT-WC05H3E5-1
KIT-WC07H3E5-1
KIT-WC09H3E5-1
KIT-WC12H6E5
KIT-WC16H6E5
Model
B4
B4
B5
B5
B6
B6
Heating capacity at +7 °C (A7/W35)
kW
3.20
5.00
7.00
9.00
12.0
16.00
COP at +7 °C (A7/W35)
5.00
4.63
4.46
4.13
4.74
4.28
Heating capacity at +2 °C (A2/W35)
kW
3.20
4.20
6.55
6.70
11.40
13.00
COP at +2 °C (A2/W35)
3.56
3.11
3.34
3.13
3.44
3.28
Heating capacity at -7 °C (A–7/W35)
kW
3.20
4.20
5.15
5.90
10.00
11.40
COP at -7 °C (A–7/W35)
2.69
2.59
2.68
2.52
2.73
2.68
Cooling capacity at 35 °C (A35/W7)
kW
3.20
4.50
6.00
7.00
10.00
12.20
EER at 35 °C (A35/W7)
3.08
2.69
2.63
2.43
2.81
2.56
Energy efficiency class
1
at 35 / 55 °C
i
*/
i
i
*/
i
i
*/
i
i
*/
i
i
/
i
i
/
i
Composite energy efficiency class
2
at 35 / 55 °C
j
/
i
j
/
i
j
/
i
j
/
i
j
/
i
j
/
i
Hydro-module
Sound pressure level
Heating / Cooling
dB(A)
28 / 28
28 / 28
30 / 30
30 / 30
33 / 33
33 / 33
Dimensions
H x L x W
mm
892 x 500 x 340
892 x 500 x 340
892 x 500 x 340
892 x 500 x 340
892 x 502 x 353
892 x 502 x 353
Weight
kg
44
44
44
44
45
46
Water-side connection
mm
28
28
28
28
28
28
High efficiency pump
Rotation speed stages
Variable
Variable
Variable
Variable
Variable
Variable
Power consumption (min./ max.)
W
30 / 100
33 / 106
34 / 114
40 / 120
34 / 110
30 / 105
Water flow rate (A7/W35)
l/min
9.2
14.3
20.1
25.8
34.4
45,9
Power of E-heating element
kW
3
3
3
3
6
6
Power consumption
Heating / Cooling
kW
0.64 / 1.04
1.08 / 1.67
1.57 / 2.28
2.18 / 2.88
2.53 / 3.56
3.07 / 4.36
Operating and start up current Heating / Cooling
A
3.0 / 4.8
5.0 / 7.6
7.2 / 10.3
10.0 / 13.0
11.5 / 16.0
13.9 / 19.5
Max. power consumption on network connection 1 / 2
A
11.0 / 13.0
12.0 / 13.0
21.0 / 13.0
22.9 / 13.0
24.0 / 26.0
25.0 / 26.0
Recommended fuse for network connection 1 / 2
A
15 / 30
15 / 30
15 / 30
15 / 30
30 / 30
30 / 30
Recommended cable cross section for network connection 1 / 2 mm²
3 x 1.5 / 3 x 1.5
3 x 1.5 / 3 x 1.5
3 x 1.5 / 3 x 1.5
3 x 1.5 / 3 x 1.5
3 x 4.0 or 6.0 / 3 x 4.0
3 x 4.0 or 6.0 / 3 x 4.0
Outdoor unit
Sound pressure level
Heating / Cooling
dB(A)
47 / 47
48 / 48
50 / 48
51 / 50
52 / 50
55 / 54
Dimensions
H x L x W
mm
622 x 824 x 298
622 x 824 x 298
795 x 900 x 320
795 x 900 x 320
1,340 x 900 x 320
1,340 x 900 x 320
Weight
kg
39
39
66
66
101
101
Line diameter
Fluid line
mm (inches)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
9.52 (3/8)
Gas line
mm (inches)
12.7 (1/2)
12.7 (1/2)
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
Pre-filled refrigerant (R410A) / CO
2
-equivalent
kg / t CO
2
-Equ. 1.20 / 2.506
1.20 / 2.506
1.45 / 3.028
1.45 / 3.028
2.55 / 5.324
2.55 / 5.324
Connection distance
m
3 – 15
3 – 15
3 – 30
3 – 30
3 – 30
3 – 30
Nominal connection distance
m
7
7
7
7
7
7
Pre-filled connection distance
m
10
10
10
10
10
10
Additional coolant fill-up quantity (R410A)
g/m
20
20
30
30
50
50
Max. height difference IU/OU
m
5
5
20
20
20
20
Operating range
Outside temperature (H / K)
°C
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
Water outlet temperature (H / K) °C
20 to 55 / 5 to 20
20 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efficiency classes is based on the official ErP specifications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been
in force since 26. September 2015. The efficiency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced starting in September 2019. Other ErP relevant
information is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Energy efficiency class scale from A++ to G.
2 Energy efficiency class including controller. Energy efficiency class scale from A+++ to D.
Summary of Contents for Aquarea B1