58
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
59
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
4.7.2 External interfaces (in-/outputs)
The Aquarea heat pumps offer the option of connecting useful accessories through external
interfaces, such as an external room thermostat or integrating the heat pump in a GLT system.
4.7.2.1 External interfaces for F- and G-Generation models
The overview of external interfaces is valid for the following models:
Split systems
Compact systems
HT
WH-SHF WH-UH09FE5
HT
WH-MHF09G3E5‘
WH-SHF WH-UH12FE5
WH-MHF12G6E5
WH-SHF WH-UH09FE8
WH-MHF09G3E8
WH-SHF WH-UH12FE8
WH-MHF12G9E8
Overview of the External Interfaces
CLOSE
OPEN
N
1 2 3 4 5 6
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21
22 23
CLOSE
OPEN
CLOSE
OPEN
N
COOL
HEA
T
N
L
N
2-way valve
3-way valve
E-Heating
element hot
water tank
Room
thermostat
Temperature
sensor for hot
water tank
Overload
protection for hot
water tank
External control
signal
Solar 3-way
valve
Solar pump
station
Terminals
Connection
Function
Condition
Cable cross
section
1 to 3
2-way valve
Output for actuation of the 2-way valve
(e.g. for floor heating, cooling)
3 × min.
0.5 mm²
4 to 6
3-way valve
Output for actuation of the 3-way valve
(e.g. for heating, domestic hot water tank)
3 × min.
0.5 mm²
Earth to 8
E-Heating element hot
water tank
Output for on/off switch of the E-heating
element hot water tank
The maximum power output of the
E-heating element hot water tank should
be maximum 3 kW.
3 × min.
1.5 mm²
9 to 12
Room thermostat
Input for room thermostat signals
4, or 3 × min.
0.5 mm²
13 to 14
Overload protection
for domestic hot water
tank
Input for overload protection of the
domestic hot water tank
The terminals 13/14 must be used if
overload protection is not used for the hot
water tank.
2 × min.
0.5 mm²
15 to 16
Temperature sensor of
the hot water tank
Input for temperature sensor of the
domestic hot water tank
2 × min.
0.5 mm²
17 to 18
Ext. control signal
Input for the external control signal
These two terminals are bridged at the
time of dispatch. Connection: 1-pin (min.
3 mm contact distance)
2 × min.
0.5 mm²
19 to 21
Solar 3-way
valve
Output for actuation of the solar 3-way
valve
3 × min.
0.5 mm²
22 to 23
Solar pump station
Input of the ON signal of solar pump 2
(230 V AC)
Use additional PCB CZ-NS1P, CZ-NS2P
or CZ-NS3P.
2 × min.
0.5 mm²
SG Ready Control
Dry contact with two inputs (Vcc-Bit1 and Vcc-Bit2). The following settings are possible:
Operating state
SG-Ready-Signal
Vcc-Bit1 Vcc-Bit2
1
Heat Pump Lock: Heat pump and E-heating element are switched off.
1
0
2 Automatic operation Heat pump runs in normal mode
0
0
3 Increased operating: Power setting 1 (in %) for heating and domestic water
0
1
4 Maximum operation: Power setting 2 (in %) for heating and domestic water
1
1
The function must be enabled through the operating unit of the heat pump. Moreover, especially the power
settings 1 and 2 should be configured via the operating unit.
Power
control
Limiting the operating current according to the current power requirement through a 0--10 Volt input signal. For
safety reasons, a minimum operating current is applied for every device. For the change between two power
stages, there is a switching hysteresis of 0.2 V (see table). The voltage values are only taken into consideration
to the first decimal place and not rounded. The valid assignments between input signal and power stage are as
follows:
Ana-
logue
input (V)
Power (%)
Ana-
logue
input (V)
Power (%)
Ana-
logue
input (V)
Power (%)
0.0
Not active
0.1 – 0.6
3.9 – 4.1
40
7.4 – 7.6
75
0.7
10
Not
active
4.2
45
40
7.7
80
75
0.8
4.3
7.8
0.9 – 1.1
10
4.4 – 4.6
45
7.9 – 8.1
80
1.2
15
10
4.7
50
45
8.2
85
80
1.3
4.8
8.3
1.4 – 1.6
15
4.9 – 5.1
50
8.4 – 8.6
85
1.7
20
15
5.2
55
50
8.7
90
85
1.8
5.3
8.8
1.9 – 2.1
20
5.4 – 5.6
55
8.9 – 9.1
90
2.2
25
20
5.7
60
55
9.2
95
90
2.3
5.8
9.3
2.4 – 2.6
25
5.9 – 6.1
60
9.4 – 9.6
95
2.7
30
25
6.2
65
60
9.7
100
95
2.8
6.3
9.8
2.9 – 31
30
6.4 – 6.6
65
9.9
100
3.2
35
30
6.7
70
65
3.3
6.8
3.4 – 3.6
35
6.9 – 7.1
70
3.7
40
35
7.2
75
70
3.8
7.3
Heating/ Cooling Switch
Dry contact for the switching between heating (contact open) and cooling (contact closed). The function must
be enabled and configured via the operating unit of the heat pump.