174
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Installation
175
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Installation
Installation example: Hydro-module WH-SDC03H3E5-1
4
2
1
3+b
c
a
A
5
6
7
B
A Connection of the power cord
1 FI switch for mains connection 1
2 FI switch for mains connection 2
3 Cable holders / cable reliefs
4 Terminal strip for connecting cable indoor unit /
outdoor unit
B Detailed view: Cable glands
5 Cable gland for power cord 1 and 2 for the connect-
ing cable between indoor and outdoor unit
6+7 Cable glands for control pipelines from optional
accessories
a Use separate cable glands for power cord and
accessory cables
b Fixing power cord with cable holders /cable reliefs
c Leave ground connector longer than the other
cables for safety reasons
6.8.1
Connecting power cord
6.8.1.1
Connecting the power cord to the indoor unit
The following method is applicable as appropriate for all indoor units, combination hydro-mod-
ules and hydro-modules of all generations, but will be explained here on the basis of the exam-
ple of a hydro-module of the H-Generation (
→
Installation example: Hydro-module, p. 175
).
Carry out the following steps to connect the power cord to the indoor unit:
1. Open the indoor unit (
→
6.5 Opening devices, p. 148
) and, if applicable, the connection
box.
2. Guide the cable through the cable gland (
5
,
a
) into the device.
3.
Secure the cable by means of the cable holder (cable reliefs) (
3
,
b
).
4. Connect the power cords 1 and 2 accordingly to mains connection 1 and 2 (
1
,
2
), accord
-
ing to the installation example below (see below) and the connection diagram following it
and ensure that the ground connector is longer than the other cables in every case (
c
).
5. Connect the connecting cable to the outdoor unit on the indoor unit terminal (
4
) and take
care to leave the ground connector longer than the other cables (
c
). Also ensure that
you connect conductors of the same cable colour to outdoor and indoor unit to the same
terminal number.
6. Connect the other end of the power cord to the power grid via the separator which is
absolutely required in all cases.
7. Secure the individual mains connections according to the cable cross section and the
maximum power consumption. Note that the separation distance between the poles must
be a minimum of 3.0 mm.