98
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
99
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
5.2.3.2 Minimum distances for compact device
Minimum distance of the compact device to the neighbouring walls and objects, showing
air flow direction
2
1
2
3
1 Minimum distance: 100 mm
2 Minimum distance: 300 mm
3 Minimum distance: 1,000 mm
Correct arrangement of multiple compact devices with representation of the air flow
direction
Wrong
Correct
1 Minimum distance: 100 mm
1
5.2.3.3
Securing the compact device
The compact device must be mounted on a flat, horizontal and solid surface. Take the weight of
the water into consideration, too, besides the weight of the device. You need four M12 anchor
bolts, with a tensile force of more than 15,000 N.
Minimum requirements for anchoring the compact device on the floor over a foundation
(A and B) or directly in the floor plate (C)
All dimensions in mm
60
mm
300
mm
>
20
80
4
3
3
4
2
1
×
100
80
0
4
3
1
5
2
355
46
0
775
980
≥
30
0
200
≥
60
×
100
80
0
4
3
1
5
2
355
46
0
775
980
≥
30
0
200
≥
60
B
C
A
A Front view: Anchoring by means of foundation
1 Flooring
2 Gravel filling
3 Strip foundation
4 Anchor bolts
5 Drain pipes
B Plan view
C Detailed view Anchoring in the floor plate