116
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
117
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Planning
5.4.2 Electric meters and rates
For connecting heat pumps to the power grid, consent should be obtained from the competent
Energy Supply Company (EVU) and connection conditions should be requested. In this context,
data regarding the building, about the heat pump and operating mode is also to be provided. If it
is possible to utilise more favourable heat pump charges, possible cut-off times and their dura-
tion are to be requested and taken into account for planning.
The power consumption of the heat pump is measured to determine the annual performance
number and for settlement of a possibly different tariff, measured by means of one’s own current
counter, to which all power connections of the heat pump are connected.
CAUTION
Danger of Water Lines Freezing Over During the Cut-off Times by EVU
If cut-off times by the Energy Supply Company (EVU) coincide with frost periods, there can be
frost damage, if the device for ensuring frost-free working is similarly affected by the cut-off time.
►
Connect booster cabinet heating or other devices for frost-free working to the power
grid such that it is not affected by the cut-off times.
5.5
Heating and cooling capacity depending on water in
-
flow and outside temperature
Key for the Performance Table
The values in the performance tables show the Panasonic measurement data matching with EN
14511-2. The data should be considered as reference values and do not offer any performance
guarantee.
t
a
: Outside temperature (°C)
P
zu
: Power consumption (kW)
t
V
: Water inflow temperature (°C)
COP: Performance number in heating mode
P
Hzg
: Heating capacity (kW)
EER: Performance number in cooling mode
P
Klg
: Cooling capacity (kW)
Performances of split systems with combination hydro-module in heating mode
Aquarea LT, combination hydro-module, single- phase, heating and cooling (ADC), Generation H
WH-ADC0309H3E5(B) / WH-UD03HE5-1
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
3.20
0.42
7.62
3.20
0.46
6.96
3.20
0.55
5.82
3.20
0.63
5.08
3.20
0.73
4.38
3.20
0.82
3.90
7
3.20
0.58
5.52
3.12
0.64
4.88
3.20
0.77
4.16
3.20
0.89
3.60
3.20
1.05
3.05
3.20
1.20
2.67
2
3.20
0.82
3.90
3.29
0.90
3.66
3.20
1.03
3.11
3.20
1.16
2.76
3.20
1.33
2.41
3.20
1.49
2.15
-7
3.20
1.08
2.96
3.58
1.19
3.00
3.20
1.34
2.39
3.20
1.48
2.16
3.20
1.67
1.92
3.20
1.86
1.72
-15
3.20
1.26
2.54
3.13
1.39
2.25
3.10
1.52
2.04
3.00
1.64
1.83
2.80
1.78
1.57
2.75
1.92
1.43
WH-ADC0309H3E5(B) / WH-UD05HE5-1
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
5.00
0.74
6.76
5.00
0.82
6.10
5.00
1.02
4.90
5.00
1.22
4.10
5.00
1.35
3.70
5.00
1.49
3.36
7
5.00
0.97
5.15
5.00
1.08
4.63
5.00
1.28
3.91
5.00
1.48
3.38
5.00
1.68
2.98
5.00
1.89
2.65
2
4.20
1.22
3.44
4.20
1.35
3.11
4.20
1.50
2.80
4.20
1.65
2.55
4.15
1.86
2.23
4.10
2.07
1.98
-7
4.20
1.46
2.88
4.20
1.62
2.59
4.00
1.72
2.33
3.80
1.82
2.09
3.70
1.95
1.90
3.55
2.08
1.71
-15
4.20
1.75
2.40
4.20
1.94
2.17
3.80
1.96
1.94
3.40
1.98
1.72
3.20
2.05
1.56
3.00
2.12
1.42
Aquarea LT, combination hydro-module, single- phase, heating and cooling (ADC), Generation H
WH-ADC0309H3E5(B) / WH-UD07HE5-1
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
7.00
0.79
8.86
7.00
0.97
7.22
6.74
1.14
5.91
6.74
1.14
5.91
6.24
1.43
4.36
6.00
1.55
3.87
7
7.00
1.43
4.90
7.00
1.57
4.46
7.00
1.84
3.81
7.00
1.84
3.81
6.90
2.35
2.94
6.80
2.59
2.63
2
6.70
1.83
3.66
6.55
1.96
3.34
6.58
2.29
2.87
6.58
2.29
2.87
6.30
2.82
2.24
6.00
3.01
1.99
-7
5.15
1.80
2.86
5.15
1.92
2.68
5.08
2.14
2.37
5.08
2.14
2.37
4.90
2.45
2.00
4.80
2.54
1.89
-15
4.60
1.87
2.46
4.60
1.98
2.32
4.60
2.19
2.10
4.60
2.19
2.10
4.55
2.63
1.73
4.50
2.86
1.57
WH-ADC0309H3E5(B) / WH-UD09HE5-1
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
9.00
1.07
8.41
9.00
1.26
7.14
8.66
1.48
5.87
8.66
1.48
5.87
8.03
1.85
4.34
7.74
2.01
3.85
7
9.00
1.93
4.66
9.00
2.18
4.13
9.00
2.49
3.62
9.00
2.49
3.62
8.95
3.25
2.76
8.90
3.70
2.41
2
6.80
1.87
3.64
6.70
2.14
3.13
6.65
2.38
2.79
6.65
2.38
2.79
6.30
2.82
2.24
6.00
3.01
1.99
-7
6.10
2.16
2.82
5.90
2.34
2.52
5.85
2.61
2.24
5.85
2.61
2.24
5.80
2.98
1.95
5.80
3.08
1.88
-15
6.00
2.55
2.35
5.90
2.66
2.22
5.65
2.82
2.00
5.65
2.82
2.00
5.20
3.08
1.69
5.00
3.18
1.57
WH-ADC1216H6E5 / WH-UD12HE5
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
12.00
1.38
8.70
12.00
1.66
7.23
11.80
1.94
6.08
11.70
2.23
5.25
11.50
2.49
4.62
11.40
2.74
4.16
7
12.00
2.10
5.71
12.00
2.53
4.74
12.00
2.96
4.05
12.00
3.39
3.54
12.00
3.78
3.17
12.00
4.16
2.88
2
11.80
3.10
3.81
11.40
3.31
3.44
11.00
3.53
3.12
10.60
3.74
2.83
9.80
3.94
2.49
9.10
4.14
2.20
-7
10.40
3.37
3.09
10.00
3.66
2.73
9.60
3.95
2.43
9.20
4.24
2.17
8.70
4.26
2.04
8.20
4.27
1.92
-15
9.30
3.46
2.69
8.90
3.62
2.46
8.50
3.79
2.24
8.10
3.95
2.05
7.50
4.05
1.85
7.00
4.16
1.68
WH-ADC1216H6E5 / WH-UD16HE5
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
16.00
2.31
6.93
16.00
2.69
5.95
16.00
3.07
5.21
16.00
3.45
4.64
16.00
3.67
4.36
15.90
3.89
4.09
7
16.00
3.21
4.98
16.00
3.74
4.28
16.00
4.27
3.75
16.00
4.80
3.33
15.20
5.11
2.97
14.50
5.41
2.68
2
13.50
3.74
3.61
13.00
3.96
3.28
12.40
4.18
2.97
11.90
4.40
2.70
10.80
4.46
2.42
9.80
4.51
2.17
-7
11.90
4.03
2.95
11.40
4.43
2.57
10.80
4.83
2.24
10.30
5.22
1.97
9.60
5.09
1.89
9.00
4.95
1.82
-15
10.60
4.09
2.59
10.30
4.38
2.35
10.00
4.67
2.14
9.70
4.96
1.96
8.80
4.94
1.78
7.90
4.91
1.61
Aquarea LT, Combination hydro-module, Three-phase, Heating and cooling (ADC), Generation H
WH-ADC0916H9E8 / WH-UD09HE8
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
9.00
1.05
8.57
9.00
1.24
7.26
8.73
1.44
6.06
8.46
1.64
5.16
8.28
1.82
4.55
8.10
2.00
4.05
7
9.00
1.54
5.84
9.00
1.86
4.84
9.00
2.16
4.17
9.00
2.46
3.66
9.00
2.76
3.26
9.00
3.06
2.94
2
9.31
2.35
3.96
9.00
2.51
3.59
9.00
2.78
3.24
9.00
3.05
2.95
8.90
3.49
2.55
8.80
3.94
2.23
-7
9.35
2.91
3.21
9.00
3.16
2.85
8.85
3.54
2.50
8.70
3.92
2.21
8.30
3.89
2.13
7.90
3.86
2.05
-15
8.65
3.06
2.83
8.30
3.21
2.59
7.95
3.41
2.33
7.60
3.61
2.11
7.15
3.71
1.93
6.70
3.81
1.76
WH-ADC0916H9E8 / WH-UD12HE8
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
12.00
1.38
8.70
12.00
1.66
7.23
11.80
1.94
6.08
11.70
2.23
5.25
11.50
2.49
4.62
11.40
2.74
4.16
7
12.00
2.10
5.71
12.00
2.53
4.74
12.00
2.96
4.05
12.00
3.39
3.54
12.00
3.78
3.17
12.00
4.16
2.88
2
11.80
3.10
3.81
11.40
3.31
3.44
11.00
3.53
3.12
10.60
3.74
2.83
9.80
3.94
2.49
9.10
4.14
2.20
-7
10.40
3.37
3.09
10.00
3.66
2.73
9.60
3.95
2.43
9.20
4.24
2.17
8.70
4.26
2.04
8.20
4.27
1.92
-15
9.30
3.46
2.69
8.90
3.62
2.46
8.50
3.79
2.24
8.10
3.95
2.05
7.50
4.05
1.85
7.00
4.16
1.68
WH-ADC0916H9E8 / WH-UD16HE8
t
V
(°C)
30
35
40
45
50
55
t
a
(°C)
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
P
Hzg
(kW)
P
zu
(kW) COP
25
16.00
2.31
6.93
16.00
2.69
5.95
16.00
3.07
5.21
16.00
3.45
4.64
16.00
3.67
4.36
15.90
3.89
4.09
7
16.00
3.21
4.98
16.00
3.74
4.28
16.00
4.27
3.75
16.00
4.80
3.33
15.20
5.11
2.97
14.50
5.41
2.68
2
13.50
3.74
3.61
13.00
3.96
3.28
12.40
4.18
2.97
11.90
4.40
2.70
10.80
4.46
2.42
9.80
4.51
2.17
-7
11.90
4.03
2.95
11.40
4.43
2.57
10.80
4.83
2.24
10.30
5.22
1.97
9.60
5.09
1.89
9.00
4.95
1.82
-15
10.60
4.09
2.59
10.30
4.38
2.35
10.00
4.67
2.14
9.70
4.96
1.96
8.80
4.94
1.78
7.90
4.91
1.61
Summary of Contents for Aquarea B1
Page 2: ...Notes ...
Page 116: ...Notes Notes ...