38
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
39
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
Product Description
Split systems with combination hydro-module / LT series / H Generation (contd.)
LT series
Three-phase (400 V / 50 Hz), heating and cooling
Combined Hydro-module
WH-ADC0916H9E8
Outdoor unit
WH-UD09HE8
WH-UD12HE8
WH-UD16HE8
Set (Combination Hydro- outdoor unit)
KIT-ADC9HE8
KIT-ADC12HE8
KIT-ADC16HE8
Model
B3
B3
B3
Heating capacity at +7 °C (A7/W35)
kW
9.00
12.00
16.00
COP at +7 °C (A7/W35)
4.84
4.74
4.28
Heating capacity at +2 °C (A2/W35)
kW
9.00
11.40
13.00
COP at +2 °C (A2/W35)
3.59
3.44
3.28
Heating capacity at -7 °C (A-7/W35)
kW
9.00
10.00
11.40
COP at -7 °C (A-7/W35)
2.85
2.73
2.57
Energy efficiency class
1
at 35 / 55 °C
i
/
i
i
/
i
i
/
i
Composite energy efficiency class
2
at 35 / 55 °C
j
/
i
j
/
i
j
/
i
Cooling capacity at 35 °C (A35/W7)
kW
7.00
10.00
12.20
EER at 35 °C (A35/W7)
3.17
2.85
2.56
Combined Hydro-module
Sound pressure level
Heating / Cooling
dB(A)
33 / 33
33 / 33
33 / 33
Dimensions
H x L x W
mm
1,800 x 598 x 717
1,800 x 598 x 717
1,800 x 598 x 717
Weight
kg
139
139
139
Water-side connection
mm
28
28
28
High efficiency pump
Rotation speed stages
Variable
Variable
Variable
Power consumption (min./ max.)
W
36 / 152
36 / 152
36 / 152
Water flow rate (A7/W35)
l/min
25.8
34.4
45,9
Power of E-heating element
kW
9
9
9
Power consumption
Heating / Cooling
kW
1.86 / 2.21
2.53 / 3.51
3.74 / 4.76
Operating and start up current Heating / Cooling
A
2.8 / 3.4
3.8 / 5.3
5.7 / 7.1
Max. power consumption on network connection 1 / 2
A
7.5 / 13.0
8.8 / 13.0
9.9 / 13.0
Recommended fuse for network connection 1 / 2
A
16 / 16
16 / 16
16 / 16
Recommended cable cross section for network connection 1 / 2 mm²
5 x 1.5 / 5 x 1.5
5 x 1.5 / 5 x 1.5
5 x 1.5 / 5 x 1.5
Domestic hot water tank
Tank volume
l
185
185
185
Max. water temperature
°C
65
65
65
Energy efficiency class
3
at 55 °C
a
a
a
Material of the tank interior
Stainless steel
Stainless steel
Stainless steel
Outdoor unit
Sound pressure level
Heating / Cooling
dB(A)
51 / 49
52 / 50
55 / 54
Dimensions
H x L x W
mm
1,340 x 900 x 320
1,340 x 900 x 320
1,340 x 900 x 320
Weight
kg
108
108
108
Line diameter
Fluid line
mm (inches)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
Gas line
mm (inches)
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
Pre-filled refrigerant (R410A) / CO
2
-equivalent
kg / t CO
2
-Equ. 2.55 / 5.324
2.55 / 5.324
2.55 / 5.324
Connection distance
m
3 – 30
3 – 30
3 – 30
Nominal connection distance
m
7
7
7
Pre-filled connection distance
m
10
10
10
Additional coolant fill-up quantity (R410A)
g/m
50
50
50
Max. height difference IU/OU
m
20
20
20
Operating range
Outside temperature (H / K)
°C
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
Water outlet temperature (H / K) °C
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efficiency classes is based on the official ErP specifications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been in
force since 26. September 2015. The efficiency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced from September 2019. Other ErP relevant informa
-
tion is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Energy efficiency class scale from A++ to G.
2 Energy efficiency class including controller. Energy efficiency class scale from A+++ to D.
3 Energy efficiency class scale from A to G.
4.6.2.3 Technical Data
Split systems with combination Hydro-module / LT series / H Generation
LT series
Single-phase (230 V / 50 Hz), Heating and Cooling
Combined Hydro-module
WH-ADC0309H3E5
WH-ADC0309H3E5B
1
WH-ADC1216H6E5
Outdoor unit
WH-UD03HE5-1
WH-UD05HE5-1
WH-UD07HE5-1
WH-UD09HE5-1
WH-UD12HE5
WH-UD16HE5
Set (Combination Hydro- outdoor unit)
KIT-ADC03H3E5(B)
KIT-ADC05H3E5(B)
KIT-ADC07H3E5(B)
KIT-ADC09H3E5(B)
KIT-ADC12HE5
KIT-ADC16HE5
Model
B1
B1
B2
B2
B3
B3
Heating capacity at +7 °C (A7/W35)
kW
3.20
5.00
7.00
9.00
12.00
16.00
COP at +7 °C (A7/W35)
5.00
4.63
4.46
4.13
4.74
4.28
Heating capacity at +2 °C (A2/W35)
kW
3.20
4.20
6.55
6.70
11.40
13.00
COP at +2 °C (A2/W35)
3.56
3.11
3.34
3.13
3.44
3.28
Heating capacity at -7 °C (A-7/W35)
kW
3.20
4.20
5.15
5.90
10.00
11.40
COP at -7 °C (A-7/W35)
2.69
2.59
2.68
2.52
2.73
2.68
Energy efficiency class
2
at 35 / 55 °C
i
* /
i
i
* /
i
i
* /
i
i
* /
i
i
/
i
i
/
i
Composite Energy efficiency class
3
at 35 / 55 °C
j
/
i
j
/
i
j
/
i
j
/
i
j
/
i
j
/
i
Cooling capacity at 35 °C (A35/W7)
kW
3.20
4.50
6.00
7.00
10.00
12.20
EER at 35 °C (A35/W7)
3.08
2.69
2.63
2.43
2.81
2.56
Combined Hydro-module
Sound pressure level
Heating / Cooling
dB(A)
28 / 28
28 / 28
28 / 28
28 / 28
33 / 33
33 / 33
Dimensions
H x L x W
mm
1,800 x 598 x 717
1,800 x 598 x 717
1,800 x 598 x 717
1,800 x 598 x 717
1,800 x 598 x 717
1,800 x 598 x 717
Weight
kg
135
135
135
135
137
137
Water-side connection
mm
28
28
28
28
28
28
High efficiency pump
Rotation speed stages
Variable
Variable
Variable
Variable
Variable
Variable
Power consumption (min./ max.)
W
30 / 120
30 / 120
30 / 120
30 / 120
36 / 152
36 / 152
Water flow rate (A7/W35)
l/min
9.2
14.3
20.1
25.8
34.4
45,9
Power of E-heating element
kW
3
3
3
3
6
6
Power consumption
Heating / Cooling
kW
0.64 / 1.04
1.08 / 1.67
1.57 / 2.28
2.18 / 2.88
2.53 / 3.56
3.74 / 4.76
Operating and start up current Heating / Cooling
A
3.0 / 4.8
5.0 / 7.6
7.2 / 10.3
10.0 / 13.0
11.5 / 16.0
16.9 / 21.3
Max. power consumption on network connection 1 / 2
A
12.0 / 13.0
12.0 / 13.0
21.0 / 13.0
22.9 / 13.0
24.0 / 26.0
26.0 / 26.0
Recommended fuse for network connection 1 / 2
A
15 / 15
15 / 15
30 / 15
30 / 15
30 / 30
30 / 30
Recommended cable cross section for network connection 1 / 2 mm²
3 x 1.5 / 3 x 1.5
3 x 1.5 / 3 x 1.5
3 x 2.5 / 3 x 1.5
3 x 2.5 / 3 x 1.5
3 x 4.0 / 3 x 4.0
3 x 4.0 / 3 x 4.0
Domestic hot water tank
Tank volume
l
185
185
185
185
185
185
Max. water temperature
°C
65
65
65
65
65
65
Energy efficiency class
4
at 55 °C
a
a
a
a
a
a
Material of the tank interior
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Outdoor unit
Sound pressure level
Heating / Cooling
dB(A)
48 / 47
49 / 48
50 / 48
51 / 50
52 / 50
55 / 54
Dimensions
H x L x W
mm
622 x 824 x 298
622 x 824 x 298
795 x 900 x 320
795 x 900 x 320
1,340 x 900 x 320
1,340 x 900 x 320
Weight
kg
39
39
66
66
101
101
Line diameter
Fluid line
mm (inches)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
9.52 (3/8)
Gas line
mm (inches)
12.7 (1/2)
12.7 (1/2)
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
Pre-filled refrigerant (R410A) / CO
2
-equivalent
kg / t CO
2
-Equ. 1.20 / 2.506
1.20 / 2.506
1.45 / 3.028
1.45 / 3.028
2.55 / 5.324
2.55 / 5.324
Connection distance
m
3 – 15
3 – 15
3 – 30
3 – 30
3 – 30
3 – 30
Nominal connection distance
m
7
7
7
7
7
7
Pre-filled connection distance
m
10
10
10
10
10
10
Additional coolant fill-up quantity (R410A)
g/m
20
20
30
30
50
50
Max. height difference IU/OU
m
5
5
20
20
20
20
Operating range
Outside temperature (H / K)
°C
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
-20 to 35 / 16 to 43
Water outlet temperature (H / K) °C
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
25 to 55 / 5 to 20
The COP details relate to 230 V in conformance with the EC Directives 2003/32/EC. Power details in conformance with EN 14511.
The information about the energy efficiency classes is based on the official ErP specifications (EU Ordinance No. 811/2013, EN 14511 and EN 14825) for heat pumps, which have been in
force since 26. September 2015. The efficiency classes marked with an asterisk (*) correspond to the new A+++ class to be introduced from September 2019. Other ErP relevant informa
-
tion is included in the respective product data sheets.
Authorised Service Partners or installation companies can activate the cooling function via a special setting.
1 Models with “B” at the end of the model denomination have an additional circulation pump as well as a mixing valve for direct connection of a second controlled heating circuit. Moreover,
the additional PCB CZ-NS4P is included in the scope of delivery.
2 Energy efficiency class scale from A++ to G.
3 Energy efficiency class including controller Energy efficiency class scale from A+++ to D.
4 Energy efficiency class scale from A to G.