3-47
D
Combining External Regeneration Resistors
Item
Regeneration absorption capacity
70 W
280 W
Combining external
regeneration
resistors
Note Use a combination with an absorption capacity larger than the average regenerative power (P
r
).
D
Dimensions (Unit: mm)
Thermal switch output
1.5 dia.
(0.3 mm
2
)
3 dia.
(0.75 mm
2
)
H
Wiring External Regeneration Resistors
Remove the short bar from between the RG and JP terminals on the Regeneration Unit and connect the
resistor(s) between the P and RG terminals.
External regeneration resistor
Short bar
Note The thermal switch output must be connected in the same way as the ALM output from the Re-
generation Unit, i.e., so that power supply is shut OFF when the contacts open. The resistor may
be damaged if the thermal switch output is used without forming a power shut-off sequence.
Operation
Chapter 3