For series connections, use the calculations below.
When 2 sets are series-connected:
•Response time (ON to OFF) :Response time of primary Response time of secondary sensor
1 -1 (ms)
•Response time (OFF to ON) :Response time (ON to OFF) x 4 (ms)
When 3 sets are series-connected:
•Response time (ON to OFF) :Response time of primary Response time of secondary sensor
2 + Response time of 3rd unit - 5 (ms)
•Response time (OFF to ON) :Response time (ON to OFF) x 5 (ms)
When 4 sets are series-connected:
•Response time (ON to OFF) :Response time of primary Response time of secondary sensor
1 + Response time of secondary sensor 2+ Response time of secondary sensor 3 - 8 (ms)
•Response time (OFF to ON) :Response time (ON to OFF) x 5 (ms)
Designation of F3SJ in series connection: p.120
Power Cable Length
Extension of power cable must be the length shown below or shorter:
Extension of the cable must be within a specified length. If it isn't, safety function may not
work properly, resulting in danger.
Condition
Single
2 connected
3 connected
4 connected
Incandescent display lamps are
used by auxiliary output and/or
external indicator output
45m
40m
30m
20m
Incandescent display lamps are
not used
100m
60m
45m
30m
Summary of Contents for F3SJ Series
Page 1: ...F3SJ A N Series Version 2 Safety Light Curtain User s Manual Cat No SCHG 719K...
Page 19: ...xvii F3SJ A User s Manual Introduction Contents E Revision History 202...
Page 20: ...xviii Introduction Contents F3SJ A User s Manual...
Page 184: ...164 Chapter 4 Wiring F3SJ A User s Manual Wiring Installation...
Page 192: ...172 Chapter 5 Wiring Examples F3SJ A User s Manual Input Output Circuit and Applications...