93
F3SJ-A
User’s Manual
Ch
apt
e
r
3
Set
ting Adjust
ed
to Appl
ication
What can be done by the setting tool
E
2. Zone Overlap Condition
A condition to configure setting zones as overlapped.
Except for combination of muting zone and fixed blanking zone (figure 3), setting zones of these 4
functions cannot be configured as overlapped. (Figure 4)
Zone overlap condition
: Setup available
x: Setting not possible
Even if a muting zone and a fixed blanking zone are configured as overlapped, fixed blanking monitoring function is
effective. Thus a fixed blanking beam receives light under muting, operation is based on setting of the monitoring
function.
Muting Function
Fixed Blanking
Function
Floating Blanking
Function
Warning Zone
Function
Muting Function
-
x
x
Fixed Blanking Function
x
x
x
Floating Blanking Function
x
x
-
x
Warning Zone Function
x
x
x
-
Muting zone
Fixed blanking zone
Floating blanking zone
Fixed blanking zone
Muting zone
Alarm zone
Figure 4
Figure 3
Summary of Contents for F3SJ Series
Page 1: ...F3SJ A N Series Version 2 Safety Light Curtain User s Manual Cat No SCHG 719K...
Page 19: ...xvii F3SJ A User s Manual Introduction Contents E Revision History 202...
Page 20: ...xviii Introduction Contents F3SJ A User s Manual...
Page 184: ...164 Chapter 4 Wiring F3SJ A User s Manual Wiring Installation...
Page 192: ...172 Chapter 5 Wiring Examples F3SJ A User s Manual Input Output Circuit and Applications...