![background image](http://html1.mh-extra.com/html/omron/e3nw-ect/e3nw-ect_operation-manual_741099139.webp)
A - 35
A Appendices
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
A-
1 Object
Dictio
nary
A
A-1-7
Manufacturer
S
pecific
Obj
e
c
ts
•
This object sets the channel display of the Sensor with the unit number that is specified by the index.
•
A value of 0000 hex is always read for this object.
•
This object sets the eco mode of the Sensor with the unit number that is specified by the index.
•
This object sets the key lock setting of the Sensor with the unit number that is specified by the index.
•
This object sets the blinking setting of the Sensor with the unit number that is specified by the index.
•
Set this object to 0001 hex to write data. It is always set to 0000 hex when reading data.
4014 + (N-1)
×
80
hex
No_01 ... 30 Channel Display
Subindex 0: Number of Entries
Range: 01 hex
Unit: ---
Default: 01 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Channel Display
Range: 0000 to 0001 hex
Unit: ---
Default: --- hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Data
Setting
0000 hex
Channel display OFF
0001 hex
Channel display ON
4015 + (N-1)
×
80
hex
No_01 ... 30 Eco Function Setting
Subindex 0: Number of Entries
Range: 01 hex
Unit: ---
Default: 01 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Eco Function Setting
Range: 0000 to FFFF hex
Unit: ---
Default: 0000 hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Data
Setting
0000 hex
Eco function OFF
0001 hex
Eco function ON
0002 hex
Eco function LO
0003 to FFFF hex
Not used.
4016 + (N-1)
×
80
hex
No_01 ... 30 Key Lock Setting
Subindex 0: Number of Entries
Range: 01 hex
Unit: ---
Default: 01 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Key Lock Setting
Range: 0000 to FFFF hex
Unit: ---
Default: --- hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Data
Setting
0000 hex
Key Lock OFF
0001 hex
Key Lock ON
0002 to FFFF hex
Not used.
4017 + (N-1)
×
80
hex
No_01 ... 30 Display Blinking
Subindex 0: Number of Entries
Range: 01 hex
Unit: ---
Default: 01 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Display Blinking
Range: 0000 to 0001 hex
Unit: ---
Default: --- hex
Attribute: A
Size: 2 bytes (U16)
Access: RW
PDO map: Not possible
Summary of Contents for E3NW-ECT
Page 1: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429 E1 07...
Page 3: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual Revised December 2017...
Page 4: ......
Page 170: ...Revision 2 E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429...
Page 171: ......