8 Troubleshooting and Maintenance
8 - 12
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
Event name
Number of Sensors Over Limit
Event code
247B 0000 hex
Meaning
Too many Sensors are connected.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
Continuously
Error attributes
Level
Minor fault
Recovery
Error reset (after
automatic slave
recovery)
Log category
System
Effects
User program
Continues.
Operation
The relevant slave will go to the Init state. I/O communica-
tions and message communications are not possible for
the relevant slave.
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
More than the maximum number of
Sensors are connected.
This event occurs when the cause of
the error is removed and communica-
tions for the relevant slave recover.
Simply reset the error in the Control-
ler.
Do not connect more than the maxi-
mum number of Sensors.
Attached
information
None
Precautions/
Remarks
None
Event name
Number of Sensors Verify Error
Event code
247C 0000 hex
Meaning
The number of Sensors that is connected does not agree with the settings.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
Continuously
Error attributes
Level
Minor fault
Recovery
Error reset (after
cycling the
power)
Log category
System
Effects
User program
Continues.
Operation
Operation continues with the Sensors that are actually
connected.
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The set value does not match the
number of Sensors that are actually
connected.
If the setting of the number of con-
nected Sensors is incorrect, correct
the set value. If the number of Sen-
sors that are connected is incorrect,
correct the Sensor connections and
cycle the power supply. If the number
of Sensors are decreased in discon-
necting Distributed Sensor Unit,
re-connect the Distributed Sensor
Unit.
Make sure that the setting of the num-
ber of connected Sensors agrees with
the number of Sensors that are actu-
ally connected.
Attached
information
None
Precautions/
Remarks
The case that the number of Sensors is decreased in disconnecting Distributed Sensor Unit is applicable. The case
that the number of Sensors is increased in connecting Distributed Sensor Unit is not applicable.
Summary of Contents for E3NW-ECT
Page 1: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429 E1 07...
Page 3: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual Revised December 2017...
Page 4: ......
Page 170: ...Revision 2 E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429...
Page 171: ......