5 EtherCAT Communications
5 - 10
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
5-5
Service Data Object (SDO)
E3NW-ECT EtherCAT Sensor Communication Units support the SDO communications.
The EtherCAT Master Unit is able to make parameter settings and monitor status by reading and writing
data from and to entries in object dictionaries via the SDO communications.
The table below shows abort codes of SDO communications errors.
The following table gives the abort codes for when sending commands to a Sensor Amplifier Unit fails.
5-5-1
Overview
5-5-2
Abort Codes
Code
Meaning
0503 0000 hex
Toggle bit not changed
0504 0000 hex
SDO protocol timeout
0504 0001 hex
Client/Server command specifier not valid or unknown
0504 0005 hex
Out of memory
0601 0000 hex
Unsupported access to an object
0601 0001 hex
Attempt to read a write only object
0601 0002 hex
Attempt to write to a read only object
0602 0000 hex
The object does not exist in the object directory.
0604 0041 hex
The object cannot be mapped into the PDO.
0604 0042 hex
The number and length of the objects to be mapped would exceed the PDO length.
0604 0043 hex
General parameter incompatibility reason
0604 0047 hex
General internal incompatibility in the device.
0606 0000 hex
Access failed due to a hardware error.
0607 0010 hex
Data type does not match, length of service parameter does not match.
0607 0012 hex
Data type does not match, length of service parameter too high.
0607 0013 hex
Data type does not match, length of service parameter too low.
0609 0011 hex
Sub-index does not exist.
0609 0030 hex
Value range of parameter exceeded (only for write access)
0609 0031 hex
Value of parameter written too high
0609 0032 hex
Value of parameter written too low
0609 0036 hex
Maximum value is less than minimum value.
0800 0000 hex
General error
0800 0020 hex
Data cannot be transferred or stored to the application.
0800 0021 hex
Data cannot be transferred or stored to the application because of local control.
0800 0022 hex
Data cannot be transferred or stored to the application because of the present device
state.
0800 0023 hex
Object dictionary dynamic generation fails or no object dictionary is present.
Value
Meaning
0800 0021 hex
An unsupported command was sent or the Sensor Amplifier Unit is in a condition under
which the command cannot be accepted. Check the command.
0609 0030 hex
A parameter value is out of range. Check the setting range of the parameter.
0800 0020 hex
A communications error or other error occurred. Implement retry processing.
Summary of Contents for E3NW-ECT
Page 1: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429 E1 07...
Page 3: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual Revised December 2017...
Page 4: ......
Page 170: ...Revision 2 E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429...
Page 171: ......