A - 31
A Appendices
E3NW-CCL CC-Link Digital Sensor Communications Unit User’s Manual (E431)
A-
4 Usin
g t
h
e Dis
tribu
ted
Se
nso
r U
n
it
A
A-4-6
Hardw
are S
pecificat
ions of the D
istributed Sensor
Unit
This switch sets the Unit address (as a decimal number) of the E3NW-DS on the DS-Bus network. The
setting range is 1 to 8. (Factory setting: 1)
If multiple Distributed Sensor Units are connected to the Sensor Communications Unit, set the
addresses of the Distributed Sensor Units in order starting from 1.
Precautions for Correct Use
•
The setting of the unit address switch is read only once when the power is turned ON.
Changing this setting after the power is turned ON will have no effect until after the next time
the power is turned ON.
•
An error will occur and operation will not continue normally if the same Unit address is
assigned to more than one Unit.
Unit Address Setting Switch
Unit Address Setting Switch