2 About the E3NW-CCL
2 - 2
E3NW-CCL CC-Link Digital Sensor Communications Unit User’s Manual (E431)
2-1
E3NW-CCL Overview
This section provides an overview of the E3NW-CCL Sensor Communications Unit.
The Sensor Communications Unit is used to monitor Sensor Amplifier Unit ON/OFF outputs and
detection levels, write parameters, and perform operations between Digital Sensors and a PLC with a
CC-Link communications interface.
The E3NW-CCL has two operating modes. The operating mode is selected via the baud rate/operating
mode setting switch.
Reduced I/O Mode: This mode allows for many devices to be connected by limiting the number of
allocated stations and allocated points.
Monitor Mode:
This mode allows for realtime monitoring and control to utilize Amplifier Unit
settings and the monitoring.
*1 This is the total number of Sensor Amplifier Units that can be connected to the Communications Unit and
Distributed Sensor Units.
Symbols: OK: Supported, NA: Not supported.
2-1-1
Features of the Sensor Communications Unit
2-1-2
E3NW-CCL Operating Modes
Operating mode
Reduced I/O Mode
Monitor Mode
CC-Link mode
Remote Network Version 1 Mode
Remote Network Version 2 Mode
Remote Network Addition Mode
Remote Network Version 2 Mode
Remote Network Addition Mode
Allocated station numbers
2
3
Number of allocated nodes
RX/RY
64
320
RWr/RWw
8
48
Expanded cyclic setting
---
Quadruple setting
Maximum connectable Communications Units in
one CC-Link system
32
21
Number of connectable Sensors
*1
16
16
Maximum connectable Distributed Sensor Units
8
8
Sensor ON/OFF status transfer
OK
OK
Simultaneous writing of the same threshold
value to more than one Sensor Amplifier Unit
OK
OK
Batch transfer of Sensor Amplifier Unit detection
levels
NA
OK
Sensor Amplifier Unit detection level peak value
and bottom value switching
NA
OK
Baud rate/operating mode setting switch
0: 156 kbps
5: 156 kbps
1: 625 kbps
6: 625 kbps
2: 2.5 Mbps
7: 2.5 Mbps
3: 5 Mbps
8: 5 Mbps
4: 10 Mbps
9: 10 Mbps
Summary of Contents for E3NW-CCL
Page 1: ...E3NW CCL CC Link Digital Sensor Communications Unit User s Manual Cat No E431 E1 08 ...
Page 114: ...A Appendices A 34 E3NW CCL CC Link Digital Sensor Communications Unit User s Manual E431 ...
Page 116: ...B B 2 E3NW CCL CC Link Digital Sensor Communications Unit User s Manual E431 ...
Page 117: ......