7 Troubleshooting and Maintenance
7 - 6
E3NW-CCL CC-Link Digital Sensor Communications Unit User’s Manual (E431)
The following tables gives the meanings of the emergency error codes used by the E3NW-CCL Sensor
Communications Unit.
7-1-4
Emergency Error Codes
E3NW-CCL Error Codes
Error code
Error name in error
history
Error details
Notification to CC-Link
master
Solution
0×01
Communications Error
Checksum error, timeout
error, etc.
The error code is stored in the
Error Information Storage
Area remote register
(RWrm+5) and the Error
Status Flag remote input relay
(RX(n+3)A in Reduced I/O
Mode and RX(n+13)A in
Monitor Mode) turns ON.
•
Retry.
•
Check
communications
with the Sensor
Unit.
0×02
Set Value Error
The command data value
is invalid. (For example, it
is out of range.)
•
Tuning failed.
•
Hysteresis width data
is out of range.
•
Timer data is out of
range.
Set the correct data.
0×04
Status Error
The Sensor Amplifier is
currently not in a state
that can accept the
command.
•
Command was
received in Setting
Mode.
•
A command for the
second point for
two-point tuning was
received, but not for
the first point.
•
A command for the
second point for
positioning tuning was
received, but not for
the first point.
Send the commands
at the correct time.
0×08
Command Error
An unsupported
command was sent to the
Sensor Amplifier Unit.
•
A command that could
not be executed was
sent.
•
A channel that does
not exist was specified.
•
Multiple Sensor Units
were specified in a
read command.
Set the correct
command.
0×10
TRG Error
TRG was turned OFF
before processing was
finished.
Keep TRG ON until
processing is
finished.