6 E3NW-CCL Function Specifications
6 - 8
E3NW-CCL CC-Link Digital Sensor Communications Unit User’s Manual (E431)
m: The address assigned to the master station in the station number settings
*1 The E9NC-TA0/AA
0/VA
0/VD
0 uses 32 bits at the same time for Sensor No.
IN1/IN2 Detection
Level/Threshold Value Areas 1 and 2.
*2 Not used on the E9NC-TA0/AA
0/VA
0/VD
0. Set to "0"
Precautions for Correct Use
The detection level obtained above is the actual detection level used for judgement. It may not
match the detection level displayed on the digital display of the Sensor Amplifier Unit.
The data that are read out to the "IN1/2 Detection Level/Threshold Value Area" with the settings of the
Detection Level/Threshold Value Switch Confirmation Area and "IN1/IN2 Switching Confirmation Area"
are shown in the table below.
FA
0/LA0/SA0/MA0/FAH0/EA
0
*1 The HIGH threshold value cannot be specified during OUT1/OUT2 area output. Use a command to read this
value.
*2 The same data is read in all cases, regardless of (1)/(2) and IN1/IN2.
TA0/AA
0/VA
0/VD
0
RWrm+2 A
Detection Level Confirmation Area
*2
2 = Detection level peak,
1 = Detection level
bottom,
0 = Current value
RWrm+2 B to 2F
Do not use.
Detection
Level/Threshold
Value Switch
Confirmation
Area
IN1/2 Detection
Level/Threshold
Value
IN1/IN2 Switch Confirmation Area
OFF = IN1
ON = IN2
ON = Threshold
value
*1
(1)
OUT1 normal detection threshold value
OUT1 area output LOW threshold value
OUT2 threshold value
OUT2 area output LOW
threshold value
(2)
Not used
Not used
OFF = Detection
level
*2
(1)
2-byte detection level
2-byte detection level
(2)
2-byte detection level
2-byte detection level
Detection
Level/Threshold
Value Switch
Confirmation
Area
IN1/2 Detection
Level/Threshold
Value
IN1/IN2 Switch Confirmation Area
OFF = IN1
ON = IN2
ON = Threshold
value
*1
(1)
Area detection LOW threshold value
(lower 2 bytes)
Normal detection threshold value (lower
2 bytes)
Not used
(2)
Area detection LOW threshold value
(upper 2 bytes)
Normal detection threshold value (upper
2 bytes)
Not used
OFF = Detection
level
*2
(1)
4-byte detection level (lower 2 bytes)
4-byte detection level
(lower 2 bytes)
(2)
4-byte detection level (upper 2 bytes)
4-byte detection level
(upper 2 bytes)
Read area: E3NW-CCL to master
Device No.
Description
Remarks
Summary of Contents for E3NW-CCL
Page 1: ...E3NW CCL CC Link Digital Sensor Communications Unit User s Manual Cat No E431 E1 08 ...
Page 114: ...A Appendices A 34 E3NW CCL CC Link Digital Sensor Communications Unit User s Manual E431 ...
Page 116: ...B B 2 E3NW CCL CC Link Digital Sensor Communications Unit User s Manual E431 ...
Page 117: ......