63
Transistor Input Units
Section 4-3
Connector Pin Arrangement
Wiring
Attach a FUJITSU connector to the Transistor Input Unit and connect it to the
external devices.
Applicable Connectors
Three types of connectors can be attached to the cable depending on the
assembly method. When creating your own cables, use one of the following
connectors.
Cables with Connectors
When a Transistor Input Unit with a high-density connector is to be connected
to an OMRON I/O Block or a Connector-Terminal Block Conversion Unit, use
the cables listed in the following table (sold separately).
Note Make sure there are no more than 16 points are turned ON at the same time.
Dimensions
Note The vertical center of the Unit is 4.9 mm lower than the center of the DIN
track. The Unit therefore extends downward 41.4 mm (including the mounting
hook) from the DIN track center.
Pin
number
Function
Pin
number
Function
A20 A19 A18 A17 A16 A15
A14 A13 A12 A11 A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
NC NC
V
IN
IN
IN
IN
IN
IN
IN
IN
V
IN
IN
IN
IN
IN
IN
IN
IN
15
14
13
12
10
09
08
11
06
05
04
03
01
00
02
07
B20 B19 B18 B17 B16 B15
B14 B13 B12 B11 B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
NC NC
V
IN
IN
IN
IN
IN
IN
IN
IN
V
IN
IN
IN
IN
IN
IN
IN
IN
15
14
13
12
10
09
08
11
06
05
04
03
01
00
02
07
m word
m+1 word
Manufacturer
Model number
Remarks
FUJITSU
FCN361J040-AU
Soldered
FCN363J040-AU
Crimp
FCN367J040-AU/F
Pressure-welded
Manufacturer
Model number
Device
OMRON
XW2Z-
@@@
B
Connector-Terminal Block Conversion
Unit
XW2B-40G4 or
XW2B-40G5
G79-I
@
C-
@
I/O Block
G7TC-I
@
16
(Unit: mm)
Approx. 70
110
60
65
27.6
37.4
12.6
35
4
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...