GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
7.
Click the Down Arrow to select the input words, the input type, and the in-
put range to be checked.
8.
Click Check.
The Check Unit Window will be displayed.
9.
Check the lower limit as follows:
• GT1-TS04T
Check that the cold contact compensator is operating at 0
°
C, then apply a
voltage equivalent to the lower limit of the conversion range to the input ter-
minal (as selected in step 7) on the Temperature Input Unit from the stan-
dard voltage/current generator.
• GT1-TS04P
Apply a resistance equivalent to the lower limit of the conversion range to
the input terminal (as selected in step 7) on the Temperature Input Unit
from the 6-dial precision resistance box.
Check that the temperature data equivalent to the voltage or resistance input
is correctly displayed as the Current Value.
10. Repeat step 9 for the median value and the upper limit.
11. To continue checking other inputs, click Close to return to the Edit Unit
Window, and then repeat steps 7 to 10.
12. When you have completed all the checks, click Close.
A message asking if you want to reset will appear. Click Yes. The Commu-
nications Unit and all I/O Units connected to it will be reset, and the Unit
will return to normal operating mode from Calibration Mode. The Edit Unit
Parameters Window for the Temperature Input Unit.
Summary of Contents for DRT1-COM
Page 1: ...OPERATION MANUAL Cat No W348 E1 05 DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL ...
Page 2: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Operation Manual Revised May 2003 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 233: ...DRT1 COM GT1 Series DeviceNet MULTIPLE I O TERMINAL Cat No W348 E1 05 OPERATION MANUAL ...