166
GT1-TS04T and GT1-TS04P Temperature Input Units
Section 5-3
Use a calibrated thermocouple in the cold junction compensator and a
compensating conductor, and set the cold junction compensator to 0
°
C.
GT1-TS04P
2.
Turn ON the power supply to all the Units of the MULTIPLE I/O TERMINAL,
including the Temperature Input Unit to be checked and the Communica-
tions Unit. Wait approximately 30 minutes until the internal temperature of
the Temperature Input Unit has stabilized.
3.
Connect the Configurator to the DeviceNet network and go online.
4.
On the device list for the Configurator, double-click the Communications
Unit to which the Temperature Input Unit is connected.
The Edit Device Parameters Window for the selected Communications
Unit will be displayed.
DeviceNet network
Communications Unit
Temperature Input Unit
6-dial precision resistance box